Chapter 1: Introduction
Environmental specifications for the S8710, S8720 and S8730 are shown in
.
Table 3: S8710/S8720/S8730 Server environmental specifications
Parameter
Air Temperature
Humidity
Electrical input
Power supply output
16 Installing and Configuring the Avaya S8500-Series Server
Description
Ambient operating: 50°F to 95°F (10°C to 35°C)
Maximum wet bulb: 82.4°F (28°C)
NOTE: All temperature ratings shown are for sea level. An altitude
derating of 1.8°F per 1000 ft to 10,000 ft (1°C per 300 meters) is
applicable. No direct sunlight is allowed.
Operating: 10% to 90%
Nonoperating: 5% to 85% (S8730: 5% to 95%)
NOTE: The storage maximum humidity of 95% is based on a
maximum temperature of 113°F (45°C). The altitude maximum for
storage corresponds to a pressure minimum of 70 kPa.
Rated input voltage:
S8710/8720:100 VAC to 240 VAC
S8730:100 to 132 VAC, 200 to 240 VAC
Rated input frequency: 50 Hz to 60 Hz
Rated input current:
S8710/8720: 6 A (110 V) to 3 A (220 V)
S8730:10 A at 100 VAC, 4.9 A at 200 VAC
Rated input power:
S8710/8720: 600 W
S8730:
980 W at 100V AC input
960 W at 200V AC input
BTUs per hour: 2050
Rated steady-state power:
S8710/8720:400 W
S8730:
800 W at 100V AC input
850 W at 120V AC input
1000 W at 200V to 240V AC input
Maximum peak power:
S8710/8720: 400 W
Table