Mitsubishi Electric FX3U-ENET-ADP User Manual page 126

Table of Contents

Advertisement

FX
-ENET-ADP User's Manual
3U
Error
Code
(decimal)
The Ethernet adapter IP address and default router IP address do not belong
764
to the same network address when the default router IP address is specified.
The Ethernet adapter IP address and external device IP address do not
765
belong to the same network address when the default router IP address is
not specified.
The Ethernet adapter IP address and SNTP server IP address do not belong
766
to the same network address when the default router IP address is not
specified.
The set value of the time zone is outside the allowable range when the SNTP
767
function is used. (Allowable range: -12:00 to 13:00)
The set value of the SNTP server IP address is wrong when the SNTP
768
function is used.
The set value of the execution time is outside the allowable range when the
769
SNTP function is used. (Allowable range: 00:00 to 23:30)
The set value of the execution interval is outside the allowable range when
770
the SNTP function is used. (Allowable range: 1 to 1440)
The specified device type used to record the error log is outside the
771
allowable range.
The set value of the number of records is outside the allowable range when
772
the error log is recorded. (Allowable range: 1 to 16)
The set value of the head device is outside the allowable range when the
773
error log is recorded.
The specified device type used to record the access log is outside the
774
allowable range.
The set value of the number of records is outside the allowable range when
775
the access log is recorded. (Allowable range: 1 to 32)
The set value of the head device is outside the allowable range when the
776
access log is recorded.
The specified device type used to record the time setting result is outside the
777
allowable range.
The set value of the head device is outside the allowable range when the
778
time setting result is recorded.
The range of devices used to record various logs (error log, access log and
779
time setting result) overlaps.
780
The host station port No. setting is wrong.
Sending is disabled because a cable is disconnected or defective (wire
815
breakage).
850
Response from the SNTP server was not received.
911
A receive error occurred in TCP/IP communication.
120
Description
Corrective action
Correct the IP address. Set the class to "A", "B"
or "C".
Specify the default router IP address.
Correct the external device IP address.
Check whether the network address is
correct.
Correct the IP address. Set the class to "A", "B"
or "C".
Correct the time zone setting.
Correct the IP address. Set the class to "A",
"B" or "C".
Specify the default router IP address.
Check the execution time setting.
Check the execution interval setting.
Check the device type setting.
Check the number of records setting.
Check the device number setting.
Check the device type setting.
Check the number of records setting.
Check the device number setting.
Check the device type setting.
Check the device number setting.
Correct the number of records and device
number of various logs (error log, access log
and time setting result).
Correct the port No.
Check whether cables are connected
correctly.
Check the hub power supply.
Check
whether
the
SNTP
connected on the network.
Correct the IP address.
Check operation of the external device.
The line may be jammed with packets. Wait
for a while, and execute sending again.
Check whether cables are connected
correctly.
9 Troubleshooting
9.3 Error Code List
ERR.
LED
On
server
is
Flicker

Advertisement