Compressed Air / Inert Gas Connection For Sweeping The Area For Electrical Equipment - Binder vdl 23 Operating Manual

Vacuum drying ovens for flammable solvents
Hide thumbs Also See for vdl 23:
Table of Contents

Advertisement

Connect the inert gas supply to the inert gas connection (adapter with hose olive diameter 8 mm / 0.31 in)
via a pressure reducer. Screw the enclosed adapter with hose olive on the thread (11) at the chamber
rear. Set the pressure reducer to a pressure slightly above ambient pressure. Make sure that the pres-
sure reducer will open. Do not alter this setting in order to avoid perturbation inside the oven and the re-
lease of large quantities of inert gas after flooding the VDL.
Overpressure in the inner chamber.
Turbulence of the charging material.
∅ Do NOT modify the atmospheric pressure setting.
4.4
Compressed air / inert gas connection for sweeping the area for electrical
equipment
The compressed air flows through the area for electrical equipment as well the preheating chamber,
which prevents a possible concentration of a solvent-containing atmosphere in the area for electrical
equipment. You can alternatively connect inert gas or nitrogen to the compressed air connection. Use
only dry gas.
In order to avoid that any oil coming from the compressed-air piping enters the vacuum drying oven, the
compressor of the compressed air system must be equipped with an oil separator, or the compressed air
system must be constructed oil-free. The condensate separator of the compressed air connection sepa-
rates water and soil from the compressed-air piping, thus leading to compressed air quality class 4 acc.
to ISO 8573-1. However, it does not prevent oil penetrating from the compressed air system, e.g. the
compressed air compressor, into the compressed-air piping. The condensate separator is equipped with
a manual condensate outlet (chap. 16.1).
Connection: Before commissioning, the existing compressed
air unit must be connected on the right side of the chamber
(hose olive ∅ 8 mm) to a compressed air line (compressed air
system) or to an inert gas supply. There must be an overpres-
sure of at least 1.5 bar / 44.3 inHg in the supply network. The
maximally permitted pressure is 7 bar / 206.7 inHg.
Immediately after connecting the compressed air or inert gas
supply, the area for electrical equipment of the oven will be
swept at 5 liters per minute. This air or inert gas quantity is used
and then released into the surrounding atmosphere permanent-
ly; independent of the oven's operating state. Therefore the
compressed air or inert gas connection on the building side
should be equipped with a stop valve that can be used to cut off
the gas supply, after having operated the drying oven.
If solvent-containing air penetrates the electrical area of the chamber, explosions may result.
Solvent-containing air penetrating the electrical area of the chamber.
Explosion hazard.
∅ Do NOT take the air for the compressed air supply from explosive atmospheres.
If the chamber is not connected to the compressed air supply, or if the specified overpressure
is not reached, it is impossible to start the VDL vacuum drying oven.
The compressed air connection is preset at the factory. Do NOT change the setting. In deliv-
ery condition of the oven, this setting is protected by a cover with seal.
If the seal is broken, please inform BINDER Service to have the setting checked and to rein-
stall the cover with seal.
VDL (E2.1) 05/2016
CAUTION
Figure 13: Compressed air connec-
tion with condensate separator
DANGER
page 34/108

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vdl 115Vdl 53

Table of Contents