5. If the problem persists and there are no other DIMMs with the same indication, replace the DIMM.
806f090c-2020ffff : [PhysicalMemoryElementName] on Subsystem [MemoryElementName]
Throttled.
Memory has been Throttled.
Severity
Warning
Serviceable
Yes
Automatically notify support
No
Alert Category
System - Other
SNMP Trap ID
22
CIM Information
Prefix: PLAT ID: 0142
User Response
Complete the following steps:
1. Check the CMM or FSM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers
are in place and correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. Make sure that the DIMM baffles are in place.
5. If the problem persists and there are no other DIMMs with the same indication, replace the DIMM.
806f090c-202101ff : [PhysicalMemoryElementName] on Subsystem [MemoryElementName]
Throttled.
Memory has been Throttled.
Severity
Warning
Serviceable
Yes
Automatically notify support
No
Alert Category
System - Other
SNMP Trap ID
22
642
Lenovo Flex System x280 X6, x480 X6, and x880 X6 Compute Node Installation and Service Guide