7.2 Requirements and Setting of Execution
7.2.1 Supported Version
In order to use the slave CPU synchronous function, the master side must support the MP2300S.
The following table shows supported versions:
Controller
MP2100
MP2100M
MP2300
MP2300S
MP2310
MP2400
MP2000 series SVB-01
7.2.2 Requirements to Execute Slave CPU Synchronous Function
In order to use the slave CPU synchronous function, both master and slave sides must meet all the following require-
ments:
( 1 ) Master Side Requirements
• Supports the slave synchronous function (the versions mentioned above and later)
• H scan setting is either an integer multiple or an integer fraction of the MECHATROLINK communication cycle
• Communication system is MECHATROLINK-II (17Byte, 32Byte)
( 2 ) Slave Side Requirements
• Selects "Slave Synchronous Function = Enable" as a MECHATROLINK communication parameter
• H scan setting is either an integer multiple or an integer fraction of the MECHATROLINK communication cycle
setting
• H scan setting is either an integer multiple or an integer fraction of the master side H scan setting
• Sets "Resume Control of Slave Synchronization = OFF" as an output register assigned to MP2300S/SVB
( 3 ) Setting Example
• Master side
Communication cycle setting : 1 ms
H scan setting
• Slave side
H scan setting
The master side H scan setting is an integral multiple of the MECHATROLINK communication cycle
The slave side H scan setting is an integer fraction of the master side H scan setting
The slave side H scan setting is an integral multiple of the communication cycle setting
→ If requirements are met, a slave CPU synchronization can be executed.
Model
JAPMC-MC2100 (-E)
JAPMC-MC2140 (-E)
JEPMC-MP2300 (-E)
JEPMC-MP2300S-E
JEPMC-MP2310-E
JEPMC-MP2400-E
JAPMC-MC2310 (-E)
: 4 ms
: 2 ms
7.2 Requirements and Setting of Execution
7.2.1 Supported Version
Version
Ver.2.60 or later
Ver.1.21 or later
7-3