2.1 Specifications

2.1.1 General Specifications

2.1 Specifications
2.1.1 General Specifications
Environmental
Conditions
Mechanical
Operating
Conditions
Electrical
Operating
Conditions
Installation
Requirements
2-2
Item
Ambient Oper-
ating Tempera-
0°C to 55°C
ture
Ambient Stor-
age Tempera-
-25°C to 85°C
ture
Ambient Oper-
30% to 95% (with no condensation)
ating Humidity
Ambient Stor-
5% to 95% (with no condensation)
age Humidity
Pollution Level
Pollution level 1 (conforming to JIS B 3501)
Corrosive Gas
There must be no combustible or corrosive gas.
Operating
2,000 m above sea level or lower
Altitude
Conforming to JIS B 3502:
• 10 to 57 Hz with single-amplitude of 0.075 mm
Vibration
• 57 to 150 Hz with fixed acceleration of 9.8 m/s
Resistance
• 10 sweeps each in X, Y, and Z directions
(sweep time: 1 octave/min.)
Conforming to JIS B 3502:
Shock Resis-
Peak acceleration of 147 m/s
tance
directions
Conforming to EN 61000-6-2, EN 55011 (Group 1, Class A)
Noise Resis-
Power supply noise (FT noise): 2 Kv min., for one minute
tance
Radiation noise (FT noise): 1 Kv min., for one minute
Ground to 100 Ω max.
Ground
Cooling Method
Natural cooling