Vega VEGABAR 54 Operating Instructions Manual page 65

Pressure transmitter
Hide thumbs Also See for VEGABAR 54:
Table of Contents

Advertisement

Weight
Max. torque threaded fittings
Output variable
Output signal
Resolution
Fault signal
Current limitation
Load
Integration time (63 % of the input
variable)
Response time
Fulfilled NAMUR recommendation
Additional output variable – temperature
Processing is made via HART multidrop, Profibus PA and Foundation Fieldbus
Range
Resolution
Input variable
Adjustment range of the zero/span adjustment:
- zero
- span
Adjustment range of the min. adjustment:
- percentage value
- pressure value
Adjustment range of the max. adjustment:
- percentage value
- pressure value
Recommended max. turn down
VEGABAR 54 - 4 ... 20 mA/HART
0,8 ... 8 kg (1.8 ... 17.6 lbs), depending on the
process fitting
25 Nm
4 ... 20 mA/HART
1.6 µA
current output unchanged; 20.5 mA; 22 mA;
<3.6 mA (adjustable)
22 mA
see load diagram in Power supply
0 ... 999 s, adjustable
150 ms (ti: 0 s, 0 ... 100 %)
NE 43
-50 ... +150°C (-58 ... +302°F)
1°C (1.8°F)
begin minus 50 % of the nominal range up to
+95 % of the nominal range
-120 ... +120 % of the nominal measuring
range
from -10 ... 110 % of the nominal measuring
range
from -50 ... 150 % of the nominal measuring
range
from -10 ... 110 % of the nominal measuring
range
from -50 ... 150 % of the nominal measuring
range
1:30 (no limitation)
-120: Values less than -1.0 bar cannot be adjusted.
12)
12)
Supplement
65