Setup with the indicating and adjustment module PLICSCOM
40
Units of measurement
bar
3 Activate the selection with [OK] and select the requested
unit with [–>] (in the example mbar).
4 Confirm with [OK] and move to position correction with
[–>].
The adjustment unit is now changed from bar to mbar.
Information:
When changing over to a height unit (in the example from bar
to m), also the density has to be entered.
Proceed as follows:
1 Push the [OK] button in the measured value display, the
menu overview is displayed.
2 Confirm the menu "Basic adjustment" with [OK], the
menu item "Units of measurement" will be displayed.
3 Activate the selection with [OK] and select the requested
unit with [–>] (in the example m).
4 Confirm with [OK], the submenu "Density unit" appears.
Units of measurement
Density unit
kg/dm³
pcf
5 Select the requested unit, e.g. kg/dm³ with [–>] and confirm
with [OK], the submenu "Density" appears.
Units of measurement
Density
0001.000
kg/dm³
6 Enter the requested density value with [–>] and [+], confirm
with [OK] and move to position correction with [–>].
The adjustment unit is now changed from bar to m.
VEGABAR 54 - 4 ... 20 mA/HART