42
Max. adjustment
+100.0 %
=
+1000.0 mbar
0000.0 mbar
Information:
The displayed pressure for 100 % corresponds to the nominal
measuring range of the sensor (in the above example 1.0 bar =
1000 mbar).
2 Set the requested % value with [–>] and [OK].
3 Edit the requested mbar value with [OK].
4 Set the requested mbar value with [+] and [–>].
5 Confirm with [OK] and move to the menu overview with
[ESC].
The max. adjustment is finished.
Information:
To adjust with a filling, you simply enter the indicated actual
measured value. If the adjustment ranges are exceeded, the
message is displayed "Outside parameter limits". The editing
procedure can be interrupted with [ESC] or the displayed limit
value can be accepted with [OK].
The setup of VEGABAR 54 is finished. All other menu items
are described in the separate operating instructions manual of
the indicating and adjustment module PLICSCOM.
VEGABAR 54 - 4 ... 20 mA/HART