Setup with the indicating and adjustment module PLICSCOM
Parameter adjust-
ment "Level meas-
urement"
38
Information:
The displayed pressure for 100 % corresponds e.g. to the
nominal range of the sensor (in the above example 1.0 bar =
1000 mbar).
2 Set the requested mbar value with [–>] and [OK].
3 Confirm with [OK] and move to the menu overview with
[ESC].
The span adjustment is finished.
Information:
To adjust with pressure, you simply enter the indicated actual
measured value. If the adjustment ranges are exceeded, the
message is displayed "Outside parameter limits". The editing
procedure can be interrupted with [ESC] or the displayed limit
value can be accepted with [OK].
The setup of VEGABAR 54 for process pressure measure-
ment is finished. All other menu items are described in the
separate operating instructions manual of the indicating and
adjustment module PLICSCOM.
Level measurement
Set up VEGABAR 54 in the following sequence:
1 Select application "Level measurement"
2 Select adjustment unit/density unit
3 Carry out position correction
4 Carrying out min. adjustment
5 Carrying out max. adjustment
In the menu item "Application" you switch over from "Process
pressure" to "Level measurement".
In the menu item "Units of measurement" you select the
physical unit in which the adjustment should be carried out, e.
g. mbar, bar, psi...
The position correction compensates the influence of the
mounting position or static pressure on the measurement. It
does not influence the adjustment values.
Information:
These steps are not necessary for instruments which are
already preset acc. to customer specifications!
VEGABAR 54 - 4 ... 20 mA/HART