4.4. Communication specification

This option occupies one station area of the buffer memory of the PLC.
There are remote I/O (RX, RY both 32 bits) and the remote register (RWw, RWr both 4
word) in the communication data for one station area.
List of remote I/O
Inverter (Slave) → PLC (Master)
Device No.
Forward running
RXn0
Reverse running
RXn1
Output terminal 1 (OUT1)
RXn2
Output terminal 2 (OUT2)
RXn3
Output terminal 3 (FL)
RXn4
Output terminal 4 (OUT3)
RXn5
Output terminal 5 (OUT4)
RXn6
Output terminal 6 (R1)
RXn7
Output terminal 7 (OUT5)
RXn8
Output terminal 8 (OUT6)
RXn9
RXnA
Output terminal 9 (R2)
RXnB
Reserved
RXnC
Monitoring
RXnD
Frequency setting completion (RAM)
RXnE
Torque setting completion (RAM)
RXnF
Instruction code execution completion
RX(n+1)0
RX(n+1)1
RX(n+1)2
RX(n+1)3
Reserved
RX(n+1)4
RX(n+1)5
RX(n+1)6
RX(n+1)7
RX(n+1)8
Reserved
RX(n+1)9
Reserved
Error status flag
RX(n+1)A
Remote station ready
RX(n+1)B
RX(n+1)C
RX(n+1)D
Reserved
RX(n+1)E
RX(n+1)F
"n" is depend on the station number.
The reserved input signal should be set OFF ("0").
RWr, RWw (Default value = 0)
RWr
Inverter → PLC
Address
RWr n First monitor value
RWr n+1 Second monitor value (output frequency)
RWr n+2 Reply code
RWr n+3 Read data
"n" is depend on the station number.
Signal
Contents
PLC (Master) → Inverter (Slave)
Device No.
Forward rotation command
RYn0
Reverse rotation command
RYn1
Input terminal 5 (S1)
RYn2
Input terminal 6 (S2)
RYn3
Input terminal 7 (S3)
RYn4
Input terminal 8 (S4)
RYn5
Input terminal 9 (L1)
RYn6
Input terminal 10 (L2)
RYn7
Input terminal 11 (L3)
RYn8
Intercept output to inverter
RYn9
(Coast stop)
RYnA
Frequency priority CC-Link
RYnB
Command priority CC-Link
RYnC
Monitor command
RYnD
Frequency setting command (RAM)
RYnE
Torque setting command (RAM)
RYnF
Instruction code execution request
RY(n+1)0
RY(n+1)1
RY(n+1)2
RY(n+1)3
Reserved
RY(n+1)4
RY(n+1)5
RY(n+1)6
RY(n+1)7
RY(n+1)8
Reserved
RY(n+1)9
Reserved
Error reset request flag
RY(n+1)A
(A reset request is during switched ON)
Reserved
RY(n+1)B
RY(n+1)C
RY(n+1)D
Reserved
RY(n+1)E
RY(n+1)F
RWw
PLC → Inverter
Address
RWw n
Monitor code (first and second)
RWw n+1
Set frequency/ torque
RWw n+2
Instruction code
RWw n+3
Write data
9  −
− 
E6581288①
Signal
Contents