5.9. Example of the inverter resetting at inverter error

The following program resets the station 1 inverter.
M9036
X0000 X000F
X0001 M126 X0020
M302 M126
M9036
*The above inverter reset using RY1A may be made only when an inverter fault occurs.
Also, inverter reset can be made independently of the operation mode.
*Change the command mode to the network operation mode.
[ FORM H0000 H00E0 K4M100 K2]
[ SET
[ SET
[ RST
[ RST
[ TO H0000 H0160 K4M200 K2
27  −
− 
Reads the remote input (RX00 to RX1F)
data of buffer memory to M100 – M131.
M226]
Switches on the error reset request flag (RY1A).
M302]
M226 ]
Switches off the error reset request flag (RY1A)
M302]
if the error status flag (RX1A) is off.
]
Writes M200 – M231 data to the remote
outputs (RY00 to RY1F) of buffer memory.