5.7. Example of the parameter reading

The following program reads f311 "Reverse-run prohibition selection" of station 2
inverter to D2.
The code of reading "Reverse-run prohibition selection" : 1311H (Hexadecimal number)
The reply code at the time of instruction code execution is set to D1.
M9036
X0000 X000F X0001 X0020
M302
Read setting
M303
M115
M9036
*To read parameters, add the triple figures that follow Fxxx to 1000H.
Example
[ FROM H0000 H00E2 K4M100
[ PLS
[ SET
[ MOV H1311
[ TO H0000 H01E6 D100 K1]
[ SET
[ FROM H0000 H02E7 D2 K1 ]
[ FROM H0000 H02E6 D1 K1 ]
[ RST
[ TO H0000 H0162 K4M200 K2]
f311 -> 1311H
25  −
− 
Reads the remote input (RX20 to RX3F)
K2 ]   data of buffer memory to M100 – M131.
M302]
M303]
D100]
Writes F311 reading code (1311H) to RWw6.
M215]
Switches on the instruction code request
request (RY2F).
"Reads F311 (RWw7) and reply code (RWr6)
to D2 and D1" when the instruction code
execution completion (RX2F) switches on.
[ RST M215]
Switches off the instruction code execution
M303]
request (RY2F).
Writes M200 – M231 data to the remote
outputs (RY20 to RY2F) of buffer memory.