Overview; Basic Specifications - Toshiba TOSVERT VF-AS1 Function Manual

Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

1. Overview

This option allows the VF-AS1 inverter to be connected into a CC-Link network. CC-Link
supports a maximum of 42 nodes, allowing for the Master unit and this option is based on
CC-Link Ver.1.10.
The CCL001Z is able to operate RUN/STOP, monitor the status of the inverter, set the
inverter's parameter and etc. by the CC-Link master through installing the VF-AS1. And it
can use different applications.

2. Basic specifications

<Environmental specification>
Item
Operating
environment
Ambient temperature
Storage temperature
Related temperature
Vibration
<CC-Link communication specification>
Number of stations
transmission distance
*Maximum number of units connected to one master station is 42 units (when only
inverters are connected).
*If any other units are included, the number of occupied stations depends on the unit and
therefore the following conditions must be satisfied:
 1. {(1×a)+(2×b)+(3×c)+(4×d)}≦64
  b:Number of units occupying 2 stations d:Number of units occupying 4 stations
 2. {(16×A)+(54×B)+(88×C)}≦2304
  A:Number of remote I/O stations
  B:Number of remote device stations
 C:Number of local, standby master
Indoors, an altitude of 3,000m or less, where the product will
not be exposed to direct sunlight, corrosive or explosive
gases, vapor, coarse particulates including dust, and where
there is no grinding fluid or grinding oil nearby.
0 to +60℃
-25 to +65℃
20 to 93% (no condensation and absence of vapor)
5 . 9 m / s
Item
Number of units
42 units max. (1 station occupied by 1 unit). May be used with
corrected
other equipment.
Baud rate
156k, 625k, 2.5M, 5M, 10Mbps
Power supply
5V DC supplied from the inverter
Station type
Remote device station
One inverter occupies one station
occupied
CC-Link dedicated cable,
Connect cable
CC-Link Ver1.10.compatiable CC-Link dedicated cable
Maximum
1200m (156kbps)
a:Number of units occupying 1 station
and intelligent device stations
Specification
2
{ 0 . 6 G } o r l e s s ( 1 0 – 5 5 H z )
Specification
(*)
c:Number of units occupying 3 stations
≦64
≦42
≦26
3  −
− 
E6581288①