SureCross DX80 and Performance DX80 Product Manual
LED 1
No LED 1

10.3 LCD Message Codes

These message codes display on the device's LCD.
Message
Solution
BAD EE
System Error. A system error typically represents a failure of the EE PROM. Contact the factory for re-
placement.
EC XX
The XX lists the Modbus register 8 message code listed in the Modbus Error Codes section.
DX80 Display shows *ERROR: The Gateway uses fully-acknowledged polling to ensure each Node RF
link is robust. If a prescribed number of sequential polling cycles are not acknowledged by a Node, the
Gateway considers the radio link with that Node to be timed out. All outputs on the Node in question
are set to the user-selected default state or the output holds its last state, depending on user configu-
ration options set using the User Configuration Tool. If the Node's RF link recovers and the Gateway or
GatewayPro determines enough acknowledged polling messages have accumulated, the link is reinsta-
ted.
No LCD
All DX80 devices display "POWER" on the LCD for the first five to ten seconds after applying power. A
DX80 Gateway always has a green LED 1 on when power is connected. DX80 Node devices flash a red
LED 2 every three seconds or a green LED 1 every second depending on the RF Link status.
Battery-powered devices turn off the LCD after fifteen minutes (factory default). Push any button to re-
activate the LCD. Battery-powered devices may be in power-down mode. To put battery powered devi-
ces into power-down mode, hold button 1 for three to five seconds. To return from power-down mode,
hold button 1 for three to five seconds.
Recheck the power connections and power requirements. Battery-powered devices require 3.6–5.5V dc.
Non-battery powered devices require 10–30V dc.
After replacing the battery, allow up to sixty seconds for the device to power up.

10.3.1 Modbus Message Codes for Register 8

Register I/O 8 is reserved for device messages or Site Survey data when in Site Survey mode.
Conditions are detected as they occur and are immediately reported back to the Gateway. Once the message is sent back
to the Gateway, the Node does not resend the message until the condition changes or there is a higher priority message.
The higher the message code, the higher the priority. For more information about how Site Survey data is stored in regis-
ters 7 and 8, refer to the Site Survey section.
The following are Modbus message codes, shown in hex, that may appear on the SureCross devices' I/O 8 Modbus regis-
ter.
Rev. J
LED 2
Definition/Solution
No LED 2
All DX80 devices display "POWER" on the LCD for the first five to ten sec-
onds after applying power. A DX80 Gateway always has a green LED 1 on
when power is connected. DX80 Node devices flash a red LED 2 every
three seconds or a green LED 1 every second depending on the RF Link
status.
If no LEDs are lighting up:
1. Put battery powered devices into power-down mode by pressing
and holding button 1 for three to five seconds. To return from
power-down mode, press and hold button 1 for three to five sec-
onds.
2. Recheck the power connections and power requirements. Battery-
powered devices require 3.6–5.5V dc. Non-battery powered devi-
ces require 10–30V dc.
3. After replacing the battery, allow up to sixty seconds for the de-
vice to power up.
4. The GatewayPro cannot be attached to another Modbus master
device or a Modbus slave ID 1 via RS-485. Special configuration
using the Web page configuration tool allows the GatewayPro to
become a slave unit when necessary.