LCD Message Codes

Problem
Solution
BAD EE
System Error. A system error typically represents a failure of the EE PROM. Contact the factory for replacement.
EC XX
The XX lists the Modbus register 8 message code listed in the Modbus Error Codes section.
DX80 Display shows *ERROR: The Gateway uses fully-acknowledged polling to ensure each Node RF link is ro-
bust. If a prescribed number of sequential polling cycles are not acknowledged by a Node, the Gateway considers
the radio link with that Node to be timed out. All outputs on the Node in question are set to the user-selected default
state or the output holds its last state, depending on user configuration options set using the User Configuration
Tool. If the Node's RF link recovers and the Gateway or GatewayPro determines enough acknowledged polling
messages have accumulated, the link is reinstated.
No LCD
All DX80 devices display "POWER" on the LCD for the first five to ten seconds after applying power. A DX80 Gate-
way always has a green LED 1 on when power is connected. DX80 Node devices flash a red LED 2 every three
seconds or a green LED 1 every second depending on the RF Link status.
Battery-powered devices turn off the LCD after fifteen minutes (factory default). Push any button to reactivate the
LCD. Battery-powered devices may be in power-down mode. To put battery powered devices into power-down
mode, hold button 1 for three to five seconds. To return from power-down mode, hold button 1 for three to five
seconds.
Recheck the power connections and power requirements. Line-powered devices require 10 to 30V dc. Battery-pow-
ered devices require 3.6 to 5.5V dc.
After replacing the battery, allow up to sixty seconds for the device to power up.

Modbus Message Codes for Register 8

Register I/O 8 is reserved for device messages or Site Survey data when in Site Survey mode.
Conditions are detected as they occur and are immediately reported back to the Gateway. Once the message is sent back to the Gate-
way, the Node does not resend the message until the condition changes or there is a higher priority message. The higher the message
rev. I
Definition/Solution
2. Check the cables connecting the GatewayPro to the host device.
All DX80 devices display "POWER" on the LCD for the first five to ten seconds
after applying power. A DX80 Gateway always has a green LED 1 on when power
is connected. DX80 Node devices flash a red LED 2 every three seconds or a
green LED 1 every second depending on the RF Link status.
If no LEDs are lighting up:
1. Put battery powered devices into power-down mode using button 1 on the
front panel. To put a battery device into power-down mode, hold button 1 for
three to five seconds. To return from power-down mode, hold button 1 for
three to five seconds.
2. Recheck the power connections and power requirements. Line powered de-
vices require 10 to 30V dc. Battery-powered devices require 3.6 to 5.5V dc.
3. After replacing the battery, allow up to sixty seconds for the device to power
up.
4. The GatewayPro cannot be attached to another Modbus master device or a
Modbus slave ID 1 via RS485. Special configuration using the Web page
configuration tool allows the GatewayPro to become a slave unit when nec-
essary.