3.5 Address list:

The contents of available addresses are shown as below:
Content
AC drive Parameters
Command
Status monitor
Read only
Address
ggnnH
gg means parameter group, nn means parameter
number, for example, the address of Pr 4-01 is
0401H. Referencing to chapter 5 for the function
of each parameter. When reading parameter by
command code 03H, only one parameter can be
read at one time.
Bit 0-1
2000H
Bit 2-3
Bit 4-5
Bit 6-15
2001H
Freq. command
Bit 0
2002H
Bit 1
Bit 2-15
2100H
Error code:
0: No errors occurred
1: Over-current (oc)
2: Over-voltage (ov)
3: Overheat (oH)
5: Overload1 (oL1)
6: External fault (EF)
7: CPU failure (cF3)
8: Hardware protection failure (HPF)
9: Current exceeds 2 times rated current during
accel (ocA)
10: Current exceeds 2 times rated current during
decel (ocd)
5-48
Functions
00: No function
01: Stop
10: Run
11: Jog + Run
Not used
00: No function
01: FWD
10: REV
11: Change direction
Not used
1: EF (external fault) on
1: Reset
Not used