Appendix A Specifications - Delta VFD-L series User Manual

Hide thumbs Also See for VFD-L series:
Table of Contents

Advertisement

SPECIFICATIONS
Voltage Class
Model Number VFD-
Applicable Motor Output (kW)
Rated Output Capacity (KVA)
Rated Output Current (A)
Max. Output Voltage (V)
Rated Frequency (Hz)
Rated Input Current (A)
Input voltage Tolerance
Frequency tolerance
Control system
Output Frequency Resolution
Torque Characteristics
Overload Endurance
Accel/Decel Time
V/F pattern
Stall Prevention Level
Keypad
Frequency
Setting
External Signal
Operation
Keypad
Setting
Signal
External Signal
Multi-function Input Signal
Multi-function Output Signal
Other Function
Protection
Other
Cooling
Installation Location
Ambient Temperature
Storage Temperature
Ambient Humidity
Vibration
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
115V
L
A/B
002
0.2
0.6
1.6
3-phase corresponds
to double input voltage
6
Single phase
90~132V 50/60Hz
SVPWM (Sinusoidal Pulse Width Modulation, carried frequency
Including the auto-torque, auto-slip compensation, starting torque can be
Potentiometer-5KΩ/0.5W, DC 0 ~ +10V (input impedance 100KΩ), 4~20mA
(output impedance 250Ω), multi-function inputs1 to 3 (3steps, JOG,
UP/DOWN command), communication setting
M0,M1,M2,M3 can be combined to offer various modes of operation,
Multi-step selection 0 to 3, Jog, accel/decel inhibit, first/second accel/decel
switch, counter, PLC Operation, external Base Block (NC,NO) selection
AC Drive Operating, Frequency Attained, Non-zero speed, Base Block,
Fault Indication, Local/Remote indication, PLC Operation indication.
AVR, S-curve, Over-Voltage Stall Prevention, DC Braking, Fault Records,
Adjustable Carried Frequency, Starting Frequency Setting of DC Braking ,
Over-Current Stall Prevention, Momentary Power Loss restart, Reverse
Inhibition, Frequency Limits, Parameter Lock/Reset
Over Voltage, Over Current, Under Voltage, Overload, Electronic thermal,
Altitude 1,000 m or below, keep from corrosive gasses, liquid and dust
9.80665m/s
004
002
004
0.4
0.2
0.4
1.0
0.6
1.0
2.5
1.6
2.5
Three-phase corresponds to input voltage
1.0~400Hz
9
4.9/1.9
6.5/2.7
Single / 3-phase
180~264V 50/60Hz
±5%
3kHz~10kHz)
0.1Hz
150% at 5 Hz
150% of rated current for 1 minute
0.1~600Sec. (can be set individually)
V/F pattern adjustable
20~200%, setting of Rated Current
ð
Setting by
Setting by RUN//STOP keys
RS-485 communication port
Overheating, Self-testing
Including EMI Filter
Forced air-cooling
-10 -40
(Non-Condensing and not frozen)
-20
to 60
Below 90%RH (non-condensing)
2
(1G) less than 20Hz, 5.88m/s
A-1
VFD-L Series
230V
007
0.7
1.6
4.2
9.7/5.1
3-phase
180~264V
50/60Hz
keys or V.R
2
(0.6Gat) 20 to 50Hz
015
1.5
2.7
7.0
*/9
A