Delta VFD-L series User Manual page 49

Hide thumbs Also See for VFD-L series:
Table of Contents

Advertisement

5 – 05
Time Duration Step 0
5 – 06
Time Duration Step 1
5 – 07
Time Duration Step 2
5 – 08
Time Duration Step 3
Settings
Pr.5-05 to Pr.5-08 correspond to operation time of each multi-step speed defined by
parameters 5-00 to 5-02. The maximum value of these parameters is 65500 sec., and
it's displayed as d 65.5.
Note:
If a parameter is set to "d0" (0 Sec), the corresponding step will be skipped. This is
commonly used to reduce number of program steps
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
d 0 to d 65500
5-31
VFD-L Series
Factory Setting: d 0
Factory Setting: d 0
Factory Setting: d 0
Factory Setting: d 0
Unit: 1 sec