VFD-L Series
Parameters
1-06
Minimum output voltage 2.0 ~ 255V
1-07
Upper bound of freq.
1-08
Lower bound of freq.
1-09
Accel time 1 (Tacc1)
1-10
Decel time 1 (Tdec1)
1-11
Accel time 2
1-12
Decel time 2
1-13
JOG Accel time
1-14
JOG Decel time
1-15
JOG frequency
1-16
Auto-accel/decel
S-curve setting in
1-17
acceleration
S-curve setting in
1-18
deceleration
Group 2: Operation Method Parameters
Parameters
2-00
Source of frequency
command
2-01
Source of operation
command
2-02
Stop method
2-03
Carrier freq.
Functions
1 ~ 110%
0 ~ 100%
0.1 ~ 600 Sec
0.1 ~ 600 Sec
0.1 ~ 600 Sec
0.1 ~ 600 Sec
0.1 ~ 600 Sec
0.0 ~ 600 Sec
1.0Hz~400Hz
0: Linear Accel/Decel
1: Auto accel, linear decel
2: Linear accel, auto decel,
3: Auto Accel/Decel
4: Linear accel. Auto decel, stall
5: Auto accel. Linear decel, stall
0 ~ 7
0 ~ 7
Functions
0: Digital keypad
1: 0 ~ 10V from AVI
2: 4 ~ 20mA from AVI
3: Controlled by V.R on drive
4: RS-485 communication interface
0: By digital keypad
1: By external terminals, keypad STOP
2: By external terminals, keypad STOP
3: By RS-485 communication interface,
4: By RS-485 communication interface,
0: Ramp stop
1: Coast stop
3 ~10K Hz
Settings
prevention during deceleration
prevention during deceleration
Settings
enable
disable
keypad STOP enable
keypad STOP disable
8-2
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
Factory
Setting
12.0
100
0.0
10.0
10.0
10.0
10.0
10.0
10.0
6.0
0
0
0
Factory
Setting
0
0
0
10

Hide quick links: