Group 6: Protection Parameters
Parameters
Over-Voltage Prevention
6-00
Level
6-01
Over-current Prevention
Level
6-02
Over-torque detection
Over-torque
6-03
level
Over-torque
6-04
time
Electronic thermal
6-05
overload relay
Electronic thermal
6-06
characteristic
6-07
Present fault record
Second
6-08
fault record
Third most recent fault
6-09
record
Forth most recent fault
6-10
record
Fifth most recent fault
6-11
record
Sixth most recent fault
6-12
record
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
Functions
0:disable
350~410V
0: disable
20~200%
0:disable
1:enable during constant speed
operation and continues until the
continuous limit is reached.
2:enabled during constant speed
operation and halted after detection.
3:enabled during accel and continues
before continuous output time limit is
reached.
4:enabled during accel and halted after
over-torque detection.
detection
30 ~ 200%
detection
0.1 ~ 10.0 Sec
0: Not used
1: Act with standard motor
2: Act with special motor
30~600 Sec
0: No fault occurred
1: oc (over current)
most
recent
2: ov (over voltage)
3: oH (over heat)
4: oL (over load)
5: oL1 (electronic thermal)
6: EF (external fault)
7: Reserved
8: Reserved
9: ocA (current exceed during
acceleration)
10: ocd (current exceed during
11: ocn (current exceed during steady
Settings
deceleration)
state)
8-5
VFD-L Series
Factory
Setting
390
170
0
150
0.1
0
8
60
0