Programming Settings; Settings For Inrush Restraint (Stabilization) - Siemens siprotec 7SJ63 Instruction Manual

Multi-functional protective relay with local control
Hide thumbs Also See for siprotec 7SJ63:
Table of Contents

Advertisement

6.5.2

Programming Settings

6.5.2.1

Settings for Inrush Restraint (Stabilization)

Ad-
LCD-Text
dress
2201
INRUSH REST.
2202
2nd HARMONIC
2203
CROSS BLOCK
2204
CROSS BLK TIMER
2205
I Max
7SJ63 Manual
C53000-G1140-C120-1
The maximum current , 0D[ where inrush restraint can operate is set at address
 ,f energizing the protected equipment results in a current that exceeds the ,
0D[ Vetting value, inrush restraint based on detection of second harmonic currents
will no longer occur.
Inrush restraint will only operate, and is only accessible, if enabled at address 
,QUXVK 5HVWUDLQW during configuration of protective functions. If the function is not
required, address  should be set to 'LVDEOHG. The function may be switched 21
or 2)) at address  ,1586+ 5(67.
Upon delivery from the factory, the device is programmed to initiate inrush restraint
when the second harmonic component of the measured current exceeds 15 % of the
total current. This value is identical for all phases and ground, and may be modified at
address  QG +$5021,&. Under normal circumstances, this setting will not need
to be changed. However, in special situations, this setting may be as low as 10 %.
If cross-blocking is desired, it can be enabled at address  &5266 %/2&.. Cross-
blocking can be activated for a specified amount of time, entered at address 
&5266 %/. 7,0(5.
The maximum current where inrush restraint can operate is set at address 
, 0D[.
In the list below, the setting range and default setting value for I Max are for an equip-
ment with a nominal current rating I
the Setting Options values and Default Setting value for I Max by 5. Consider the cur-
rent transformer ratios when setting the equipment with primary values.
Setting options
OFF
ON
10 ~ 45%
No
Yes
0.00 ~ 180.00 sec.
1.50 ~ 125.00 A
= 5 A. For a nominal current rating I
N
Default Setting
OFF
Switch-on Inrush stabilization
15%
Component of 2nd harmonic for In-
rush recognition
No
Blocking per crossblock function
0.00 sec.
Blocking time for crossblock function
37.50 A
Maximum current for inrush recogni-
tion
Functions
= 1 A, divide
N
Comment
6-71