Addr.
LCD-Text
1515
Normal Load
(Torque angle of
dir. Fct)
1516
67 Direction
1530
67 TOC User PU
1531
MofPU Res T/Tp
7SJ63 Manual
C53000-G1140-C120-1
Setting Options
Default Setting
Inductive (135°)
Inductive (135°)
Resistive (90°)
Capacitive (45°)
Forward
Forward
Reverse
Comments
Angle of the directional limit line X X X X X
Directional orientation of the 67
elements
67-TOC user defined character-
istic curve values
67-TOC reset user defined
curve values
Functions
Configuration
X X X X X
X X
X
6-55