Advertisement

Commands
7SJ63 Manual
C53000-G1140-C120-1
Circuit Breaker
52
52a
V+
V–
(breaker)
Single Point Indication (SP)
Figure 5-3
Input Indications (SP & DP)
Commands (control actions) are output indications which are specially configured for
the transmission of control signals to switching devices (circuit breakers, etc.).
q
For each device to be controlled, determine if switching is to be done with 1 contact,
1
1
/
contacts (single contact and common), or 2 contacts; with a single or double
2
command; and with or without feedback signals. See Table 5-1 and Figures 5-4 to
5-12. The information to be processed and the command type are determined with
these decisions.
q
Assign the necessary binary inputs and outputs in the SIPROTEC
specific function. Important to note are:
− Messages and commands associated with a switching device must always occu-
py sequential binary inputs and outputs in the SIPROTEC
− The TRIP (OFF)–command is always configured prior to the associated CLOSE
(ON)–command;
− Limitations may arise because of the commoning of some binary inputs and out-
puts in the SIPROTEC
When the types of commands have been established, DIGSI
sponding number of relay outputs contacts. For this, the corresponding output con-
tacts are numbered consecutively. This must be observed when wiring the relays to
the corresponding equipment to be controlled.
Table 5-1 shows the most important command types. They are made available as op-
tions in the Configuration Matrix for the SIPROTEC
for Switching Devices" in Sub-section 5.2.4). All double commands, with and without
feedback indications, are also available as transformer step commands. The following
Figures 5-4 through 5-12 show time diagrams, control settings, and the sequence of
relay positioning in the configuration matrix for frequently used command types.
Table 5-1
Most Important Command Types
Single Command with Single
Output
Double Command with Single
Outputs
Double Command with Single
Outputs plus Common Output
Double Command with Single
Outputs and Common Bus Output
(7SJ63)
V+
Binary Input (BI1)
V–
®
device.
With 1 contact
With 2 contacts
With 3 contacts
Minimum 3
contacts
Configuration
Circuit Breaker
(7SJ63)
52
Binary Input (BI 2)
52b
52a
(breaker)
Binary Input (BI 3)
Double Point Indication (DP)
®
device to the
®
device;
®
4 reserves a corre-
®
device (see also "Binary Outputs
without feedback
with feedback
without feedback
with feedback
without feedback
with feedback
without feedback
with feedback
&B6
&)B6
&B'
&)B'
&B'
&)B'
C_D2
CF_D2
5-7