Installation and Commissioning
8-34
Figure 8-18
Dialog Box: Generate indications
The Indication column displays all of the messages that are configured (masked) for
the SCADA interface in the matrix. The SETPOINT status column shows the value of
each message. The values available depend on the message type. Most values are
either ON or OFF. The value of a message to be sent can be changed by clicking on
the field for the value, and selecting the desired option from the drop-down list.
Warning!
Messages issued over the SCADA interface using the System Interface Test appear
as actual operational messages sent by the SIPROTEC
tem design, the result could be the operation of primary equipment including circuit
breakers or disconnectors. Knowledge of the system design is therefore important. If
undesired operations can occur during the testing, then outputs of the SIPROTEC
device must be manually disconnected.
The first time a button is clicked in the Action column to send a message, Password
No. 6 (for hardware test menus) is requested. After correct input of the password, mes-
sages can be individually transmitted. To send a message, click on the Action button
of the corresponding line. The corresponding message is then sent. The message can
be read in the Event Log of the SIPROTEC
The capability of sending further messages remains until the dialog box is closed.
®
device. Depending on sys-
®
device and in the SCADA.