Siemens siprotec 7SJ63 Instruction Manual page 547

Multi-functional protective relay with local control
Hide thumbs Also See for siprotec 7SJ63:
Table of Contents

Advertisement

Addr.
Setting Title
2202
2nd HARMONIC
2203
CROSS BLOCK
2204
CROSS BLK TIMER
2205
I Max
3101
Sens. Gnd Fault
3102
CT Err. I1
3103
CT Err. F1
3104
CT Err. I2
3105
CT Err. F2
3106
VPH MIN
3107
VPH MAX
3109
64-1 VGND
3110
64-1 VGND
3111
T-DELAY Pickup
3112
64-1 DELAY
3113
50Ns-2 PICKUP
3114
50Ns-2 DELAY
3115
67Ns-2 DIRECT.
3117
50Ns-1 PICKUP
3118
50Ns-1 DELAY
3119
51Ns PICKUP
3120
51Ns TIME DIAL
3122
67Ns-1 DIRECT.
3123
RELEASE DIRECT.
3124
PHI CORRECTION
3125
MEAS. METHOD
3126
RESET DELAY
3130
PU CRITERIA
3131
M.of PU TD
4001
FCT 46
7SJ63 Manual
C53000-G1140-C120-1
Setting Options
Default Setting
10..45 %
15 %
NO
NO
YES
0.00..180.00 sec
0.00 sec
1.50..125.00 A
37.50 A
OFF
OFF
ON
Alarm Only
0.003..1.600 A
0.050 A
0.0..5.0 °
0.0 °
0.003..1.600 A
1.000 A
0.0..5.0 °
0.0 °
10..100 V
40 V
10..100 V
75 V
1.8..130.0 V
40.0 V
10.0..225.0 V
70.0 V
0.04..320.00 sec
1.00 sec
0.10..40000.00 sec
10.00 sec
0.003..1.500 A
0.300 A
0.00..320.00 sec
1.00 sec
Forward
Forward
Reverse
Non-Directional
0.003..1.500 A
0.100 A
0.00..320.00 sec
2.00 sec
0.003..1.400 A
0.100 A
0.10..4.00 sec
1.00 sec
Forward
Forward
Reverse
Non-Directional
0.003..1.200 A
0.010 A
-45.0..45.0 °
0.0 °
COS Phi
COS Phi
SIN phi
0..60 sec
1 sec
Vgnd OR INs
Vgnd OR INs
Vgnd AND INs
OFF
OFF
ON
Comments
2nd. harmonic in % of fundamental
Cross Block
Cross Block Time
Maximum Current for Inrush Restraint
Sensitive Ground Fault
Current I1 for CT Angle Error
CT Angle Error at I1
Current I2 for CT Angle Error
CT Angle Error at I2
L-Gnd Voltage of Faulted Phase Vph
Min
L-Gnd Voltage of Unfaulted Phase Vph
Max
64-1 Ground Displacement Voltage
64-1 Ground Displacement Voltage
Time-DELAY Pickup
64-1 Time Delay
50Ns-2 Pickup
50Ns-2 Time Delay
67Ns-2 Direction
50Ns-1 Pickup
50Ns-1 Time delay
51Ns Pickup
51Ns Time Dial
67Ns-1 Direction
Release directional element
Correction Angle for Dir. Determination
Measurement method for Direction
Reset Delay
Sensitive Ground Fault PICKUP criteria
Multiples of PU
Time-Dial
46 Negative Sequence Protection
Appendix
A-53

Advertisement

Table of Contents
loading

Table of Contents