8 Maintenance and service
8.1 Safety checks
64
8

Maintenance and service

8.1

Safety checks

The following safety checks must be performed every 24 months by a
qualified service engineer:
● Visual inspection of the unit and its accessories for mechanical
Up to 3W
damage that might impair operation
● General function check
● Check of the visual and audible indicators
● NC and SFC earth leakage current acc. to IEC 60601
● NC and SFC housing leakage current acc. to IEC 60601
● NC and SFC patient leakage current acc. to IEC 60601
● Laser power measurement with a calibrated measuring instrument in
the range between 0.2 W and 3 W
8.2

Maintenance

The SIROLaser Blue does not require special maintenance. In case of
Maintenance table, Sirona
malfunctioning, see chapter Technical support, repair and testing.
However, Sirona Dental Systems GmbH recommends taking the
following actions at regular intervals:
Action
Check of the single-use
fiber tips or therapy light
guides, see "Assembly of
sterile single-use optical
fiber tips [ → 28]" and
"Assembly of therapy light
guides [ → 32]"
Calibration check of the
laser, see "Laser
calibration check [ → 50]"
Recommended check of
the optical power at the end
of the single-use fiber tip
with an external power
meter, see "Laser
calibration check [ → 50]"
Safety checks (required by
law in some European
countries)

Sirona Dental Systems GmbH

Operating Instructions SIROLaser Blue
Frequency
Conducting personnel
Before each
System owner
treatment session
Weekly
System owner
Every twelve
System owner
months
Every 2 years
Sirona Dental
Systems GmbH, local
Dental Sales or
qualified service
engineer.