Typical Connection Arrangement - GE EntelliGuard G Installation, Operation And Maintenance Manual

Power circuit breaker
Hide thumbs Also See for EntelliGuard G:
Table of Contents

Advertisement

1.3.4: Typical Connection Arrangement

1.3.4: Ligação Típica Tomadas Standard
1.3.4: Conexionado típico Tomas estándar
Anilha de Segurança
Arandela de seguridad
Customer bus
Barramento Exterior
Embarrado exterior
Customer bus
Barramento Exterior
Embarrado exterior
Plain Washer (Heavy duty)
Anilha plana (alta resistência)
Arandela plana (alta resistencia)
Breaker type 'Automatic' Switch Type
Disjuntor
Interruptor de corte em carga Tamanho
Interruptor automático Interruptor en carga
-----------------------------------------------------------------------------------------------------
GG04, S N & H
GJ04S & GW04N
GG04 E & M
GJ04H
GG07, S N & H
GJ07S & GW07N
GG07 E & M
GJ07H
GG08, S N & H
GJ08S & GW08N
GG08 E & M
GJ08H
GG10, S N & H
GJ10S & GW10N
GG10 E & M
GJ10H
GG13, S N & H
GJ13S & GW13N
GG13 E & M
GJ13H
GG16, S N & H
GJ16S & GW16N
GG16 E & M
GJ16H
GG20, S N & H
GJ20S & GW20N
GG20 E & M
GJ20H
GG25N, H & M
GJ25N & GW25H
GG32N, H & M
GJ32N & GW32H
GH32N, H & M
GK32N & GZ32H
GG32G & L
GJ32G
GG40N, H & M
GJ40N & GW40H
GH40N, H & M
GK40N & GZ40H
GG40G & L
GJ40G
GG50M & L
CJ50L
GG64M & L
CJ64L
Lock Washer
Envelope
In (A)
In (A)
Tamaño
In (A)
1 or/ó 2
400
1 or
2
400
1 or
2
630
1 or
2
630
1 or
2
800
1 or
2
800
1 or
2
1000
1 or
2
1000
1 or
2
1250
1 or
2
1250
1
1600
2
1600
1
2000
2
2000
2
2500
2 or
3
3200
2 or
3
3200
2 or
3
3200
2
4000
2
4000
3
4000
3
5000
3
6400
BREAKER
Hex Bolt (8.8)
Parafuso Sextavado (8.8)
Tornillo Hex. (8.8)
Breaker terminal
Tomadas Disjuntor
Toma interruptor
Hex Nut (8.8)
Porca Sextavada (8.8)
Tuerca Hex (8.8)
Recommended Copper Bus Bar sizes
Tamanhos recomendados de barra de cobre
Tamaños recomendados de barra de cobre
[or = ou = ó]
-----------------------------
1 x 40 x 10 or 1 x 80 x 5 or 2 x 40 x 5
1 x 40 x 10 or 1 x 80 x 5 or 2 x 40 x 5
1 x 50 x 10 or 1 x 100 x 5 or 2 x 50 x 5
1 x 50 x 10 or 1 x 100 x 5 or 2 x 50 x 5
1 x 50 x 10 or 1 x 100 x 5 or 2 x 50 x 5
1 x 50 x 10 or 1 x 100 x 5 or 2 x 50 x 5
1 x 60 x 10 or 2 x 60 x 5
1 x 60 x 10 or 2 x 60 x 5
2 x 40 x 10 or 2 x 80 x 5
2 x 40 x 10 or 2 x 80 x 5
2 x 50 x 10 or 2 x 100 x 5
2 x 50 x 10 or 2 x 100 x 5
3 x 50 x 10 or 3 x 100 x 5
3 x 50 x 10 or 3 x 100 x 5
4 x 50 x 10 or 4 x 100 x 5
4 x 100 x 10
4 x 100 x 10
4 x 100 x 10
4 x 100 x 10 + 1 x 100 x 5
4 x 100 x 10 + 1 x 100 x 5
4 x 100 x 10
5 x 120 x 10 or 6 x 100 x 10
7 x 120 x 10 or 8 x 100 x 10
EntelliGuard G
1
.3
Recommended Connection Cross
sections
The adjacent table indicates the
recommended bus bar dimensions
to be used in connecting the
EntelliGuard G™ Power Circuit
Breaker.
Secções de ligação
recomendadas
A tabela adjacente indica as
dimensões recomendadas de
barra para serem usadas na
ligação do
Disjuntor EntelliGuard G™.
Secciones recomendadas
La tabla adjunta indica las
secciomes recomendadas de
las barras a utilizar para la
conexión del Interruptor de
bastidor EntelliGuard G™
1.3-05