Fault Condition
Force Fault
Network Link Down
Connection Time-out
Duplicate IP Address
Default MAC Address
Two drive monitor parameters, U6-98 and U6-99, assist the user in network troubleshooting.
• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared
upon drive power-up.
• U6-99 displays the present option status. U6-99 is cleared upon a network-issued fault
reset and upon power-up.
If another fault occurs while the original fault is still active, parameter U6-98 retains the
original fault value and U6-99 stores the new fault status value.
YASKAWA ELECTRIC TOBP C730600 59A V1000 Option Modbus TCP/IP Installation Manual
Status Value
Fault Declared
(U6-98/U6-99)
EF0
BUS ERROR
BUS ERROR
BUS ERROR
None
Network sent a message to force this node to the
3
fault state
1200
No network link to the option
1201
The control connection timer (F7-16) timed out
This node and at least one other node have the same
1202
IP address
Factory default MAC Address programmed into the
1203
option. Contact a Yaskawa representative or the
nearest Yaskawa sales office for details.
9 Troubleshooting
Description
EN 43