Control Connection
Time-out.
Duplicate IP Address
LED Operator Display
EF0
Cause
An external fault is being
sent from the upper
controller (PLC)
Problem with the PLC
program
LED Operator Display
oFA00
Cause
Non-compatible option
connected to the drive
LED Operator Display
oFA01
Cause
Problem with the
connectors between the
drive and option
LED Operator Display
oFA03
Cause
Option hardware fault
YASKAWA ELECTRIC TOBP C730600 59A V1000 Option Modbus TCP/IP Installation Manual
• Option did not receive a command (write to Modbus address 01H) within the time-out
period specified in parameter F7-16
• Check value programmed in F7-16
• Check if PLC program stopped running
The option shares IP Address with at least one other node.
Check the setting value of F7-03 and F7-04.
Option Card External Fault
The alarm function for an external device has been triggered.
• Remove the cause of the external fault
• Reset the external fault input from the PLC device
Check the program used by the PLC and make the appropriate corrections.
Option Card Fault
Option is not properly connected.
Connect an option that is compatible with the drive.
Option Card Fault
Option is not properly connected.
Turn the power off and check the connectors between the drive and option.
Option Card Fault
Option self-diagnostics error.
Replace the option.
9 Troubleshooting
Fault Name
Corrective Action
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
EN 41