The use of CAT5e or equivalent Shielded Twisted Pair (STP) cable is
recommended.
Connection Diagram
V1000
EtherNet/IP Master EtherNet/IP Cable
<1> The ground wire provided in the option shipping package must be connected during
installation.
15.
Attach the option cover by aligning the tabs with the mounting holes, seat the front
cover into place, and tighten the screw on the front.
Figure 19
Note: Take proper precautions when wiring the option so that the front covers will easily fit back onto
the drive. Make sure no cables are pinched between the front covers and the drive when
replacing the covers.
16.
Set drive parameters in Table 6 for proper option performance.
YASKAWA ELECTRIC TOBP C730600 59A V1000 Option Modbus TCP/IP Installation Manual
Power
Figure 19 Wiring Diagram
V1000
Figure 20 Attach the Option Cover
5 Installation Procedure
R
U
S
V
T
W
V1000
<1>
SI-EN3/V
EtherNet/IP
Option
FE
Tabs should line up
Motor
M
EN 27