YASKAWA V1000 Installation Manual page 30

Tcp/ip
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

6 Related Drive Parameters
No.
(Addr. H)
F7-14
Duplex Mode Selection
(3F2)
F7-15
Communication Speed
(3F3)
Selection
<7>
F7-16
Communication Loss Time-
(3F4)
out
H5-11
Communications ENTER
(43C)
Function Selection
<1> To start and stop the drive with the option master device using serial communications, set b1-02 to 3. To control
the drive frequency reference via the master device, set b1-01 to 3.
<2> If F6-01 is set to 3, the drive will continue to operate when a fault is detected. Take safety measures, such as
installing an emergency stop switch.
<3> Cycle power for setting changes to take effect.
<4> If F7-13 is set to 0, then all IP Addresses (F7-01 to F7-04) must be unique.
<5> Set F7-01 to F7-12 when F7-13 is set to 0.
<6> Default setting differs by drive software version.
1012 to 1015: 0
1016: 1
<7> Set F7-15 when F7-14 is set to 0 or 2.
<8> The setting values differ by drive software version.
1012 to 1015
Default: 0
Range: 0, 10, 100
1016
Default: 10
Range: 10, 100
EN 30
Name
Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate duplex mode and
communication speed
2: Full duplex forced
Sets the communication speed.
0: 10 Mbps (Available only with drive software
version PRG: 1012 to 1015)
1: 10 Mbps
100: 100 Mbps
Sets the time-out value for communication loss
detection in tenths of a second. A value of 0
disables the connection time-out.
Example: An entered value of 100 represents 10.0
seconds.
Select the function for the ENTER command that
saves parameter data to the drive.
0: Parameter changes are activated when ENTER
command is written
1: Parameter changes are activated immediately
without use of ENTER
command
YASKAWA ELECTRIC TOBP C730600 59A V1000 Option Modbus TCP/IP Installation Manual
Description
Values
Default:
<6>
Range: 0 to 2
Default:
<8>
Range:
<8>
Default: 0
Min.: 0
Max.: 300
Default: 1
Range: 0, 1