Vega VEGABAR 66 Operating Instructions Manual page 42

Foundation fieldbus
Table of Contents

Advertisement

6 Set up with the indicating and adjustment module PLICSCOM
Carry out span adjust-
ment
42
Zero
000.0 %
=
P
+0000.0 mbar
0000.0 mbar
2
Set the requested mbar value with [+] and [->].
3
Confirm with [+] and move to span adjustment with [->].
The zero adjustment is finished.
Information:
The zero adjustment shifts the value of the span adjustment. The span,
i.e. the difference between these values, however, remains un-
changed.
Information:
For an adjustment with pressure, simply enter the actual measured
value indicated at the bottom of the display.
If the adjustment ranges are exceeded, the message "Outside
parameter limits" appears. The editing procedure can be aborted with
[ESC] or the displayed limit value can be accepted with [OK].
Proceed as follows:
1
Edit the mbar value in the menu item "span" with [OK].
Span
100.0 %
=
P
+1000.0 mbar
0000.0 mbar
Information:
The displayed pressure for 100 % corresponds to the nominal
measuring range of the sensor (in the above example 1 bar =
1000 mbar).
2
Set the requested mbar value with [->] and [OK].
3
Confirm with [OK] and move to the menu overview with [ESC].
The span adjustment is finished.
Information:
For an adjustment with pressure, simply enter the actual measured
value indicated at the bottom of the display.
If the adjustment ranges are exceeded, the message "Outside
parameter limits" appears. The editing procedure can be aborted with
[ESC] or the displayed limit value can be accepted with [OK].
VEGABAR 66 • Foundation Fieldbus