Operating Instructions

Pressure transmitter with ceramic
measuring cell
VEGABAR 82
Foundation Fieldbus
Document ID: 45032

Advertisement

Table of Contents
loading

Summary of Contents for Vega VEGABAR 82

  • Page 1: Operating Instructions

    Operating Instructions Pressure transmitter with ceramic measuring cell VEGABAR 82 Foundation Fieldbus Document ID: 45032...
  • Page 2: Table Of Contents

    Parameter adjustment - Quick setup ................38 Parameter adjustment - Extended adjustment..............39 Saving the parameterisation data ................... 50 Setup with PACTware ......................51 Connect the PC ......................51 Parameter adjustment ....................51 Saving the parameterisation data ................... 52 VEGABAR 82 • Foundation Fieldbus...
  • Page 3 11.6 Industrial property rights ....................95 11.7 Trademark ........................95 Safety instructions for Ex areas Take note of the Ex specific safety instructions for Ex applications. These instructions are attached as documents to each instrument with Ex approval and are part of the operating instructions manual. Editing status: 2017-11-14 VEGABAR 82 • Foundation Fieldbus...
  • Page 4: About This Document

    Symbols used Document ID This symbol on the front page of this instruction refers to the Docu- ment ID. By entering the Document ID on www.vega.com you will reach the document download. Information, tip, note This symbol indicates helpful additional information.
  • Page 5: For Your Safety

    During work on and with the device the required personal protective equipment must always be worn. Appropriate use The VEGABAR 82 is a pressure transmitter for process pressure and hydrostatic level measurement. You can find detailed information about the area of application in chapter "Product description". Operational reliability is ensured only if the instrument is properly used according to the specifications in the operating instructions manual as well as possible supplementary instructions.
  • Page 6: Eu Conformity

    NE 107 - Self-monitoring and diagnosis of field devices For further information see www.namur.de. Installation and operation in the USA and Canada This information is only valid for USA and Canada. Hence the follow- ing text is only available in the English language. VEGABAR 82 • Foundation Fieldbus...
  • Page 7: Environmental Instructions

    That is why we have introduced an environment management system with the goal of continuously improving company environmental pro- tection. The environment management system is certified according to DIN EN ISO 14001. Please help us fulfil this obligation by observing the environmental instructions in this manual: • Chapter "Packaging, transport and storage" • Chapter "Disposal" VEGABAR 82 • Foundation Fieldbus...
  • Page 8: Product Description

    Alternatively, you can access the data via your smartphone: • Download the VEGA Tools app from the "Apple App Store" or the "Google Play Store" • Scan the Data Matrix code on the type label of the instrument or •...
  • Page 9: Principle Of Operation

    Optional instrument features are also described in this operating instructions manual. The respective scope of delivery results from the order specification. Principle of operation Measured variables The VEGABAR 82 is suitable for the measurement of the following process variables: • Process pressure •...
  • Page 10 Fig. 3: Electronic differential pressure measurement through Master/Slave combination You can find detailed information in the operating instructions of the respective slave sensor. Application area VEGABAR 82 is suitable for applications in virtually all industries. It is used for the measurement of the following pressure types. • Gauge pressure •...
  • Page 11 Pressure types The measuring cell design depends on the selected pressure type. Relative pressure: the measuring cell is open to the atmosphere. The ambient pressure is detected in the measuring cell and compen- sated. It thus has no influence on the measured value. VEGABAR 82 • Foundation Fieldbus...
  • Page 12 Seal for the measuring cell Additional, front seal for measuring cell Diaphragm Process fitting Seal for the process fitting Front-flush mounting with The front-flush installation is particularly suitable for applications with single seal viscous and abrasive media and in case of buildup. The measuring cell seal is positioned laterally. VEGABAR 82 • Foundation Fieldbus...
  • Page 13 Seal for the measuring cell Seal for the process fitting Process fitting Diaphragm Front-flush mounting with The front-flush installation is particularly suitable for applications with double seal viscous media. The additional, front sealing protects the glass joint of the measuring cell against chemical attack and the measuring cell electronics against diffusion of aggressive gases from the process. VEGABAR 82 • Foundation Fieldbus...
  • Page 14 Gap-free seal for process fitting Process fitting Diaphragm Installation in hygienic The front-flush, hygienic installation of the measuring cell acc. to 3A fitting acc. to 3-A is particularly suitable for food applications. The sealings are installed gap-free. The additional front sealing for the measuring cell protects also the glass joint. A hole in the process fitting is used for leakage detection. VEGABAR 82 • Foundation Fieldbus...
  • Page 15: Packaging, Transport And Storage

    Technical data - Ambient conditions" • Relative humidity 20 … 85 % Lifting and carrying With an instrument weight of more than 18 kg (39.68 lbs) suitable and approved equipment must be used for lifting and carrying. VEGABAR 82 • Foundation Fieldbus...
  • Page 16: Accessories And Replacement Parts

    Slave sensors of VEGABAR series 80 enable in conjunction with VEGABAR 82 an electronic differential pressure measurement. You can find further information in the operating instructions of the respective slave sensor. VEGADIS 81 The VEGADIS 81 is an external display and adjustment unit for VEGA plics sensors. ® For sensors with double chamber housing the interface adapter "VEGADIS adapter"...
  • Page 17 VEGABAR series 80" (Document-ID 45054). Supplementary elec- The supplementary electronics is a replacement part for sensors with tronics for Foundation Foundation Fieldbus and double chamber housing. Fieldbus You can find further information in the operating instructions "Supple- mentary electronics for Foundation Fieldbus" (Document-ID 45111). VEGABAR 82 • Foundation Fieldbus...
  • Page 18: Mounting

    The free openings for the cable glands are therefore covered with red dust protection caps as transport protection. The dust protection caps do not provide sufficient protection against moisture. VEGABAR 82 • Foundation Fieldbus...
  • Page 19: Ventilation And Pressure Compensation

    Filter elements Ventilation and pressure compensation are carried out with VEGABAR 82 via a filter element. It is air permeable and moisture- blocking. Caution: The filter element causes a time-delayed pressure compensation. When quickly opening/closing the housing cover, the measured value can change for approx. 5 s by up to 15 mbar. For effective ventilation, the filter element must always be free of buildup. VEGABAR 82 • Foundation Fieldbus...
  • Page 20 Instruments in protection IP 66/IP 68 (1 bar) - ventilation via capil- laries in non-detachable cable • Instruments with absolute pressure Instruments in Ex-d ver- The filter element is integrated in the process assembly. It is located in sion a rotatable metal ring and has the following function: • Atmospheric pressure compensation (with relative pressure meas- uring ranges) VEGABAR 82 • Foundation Fieldbus...
  • Page 21 The filter element is mounted into the electronics housing. It has the following functions: • Ventilation of the electronics housing • Atmospheric pressure compensation (with relative pressure meas- uring ranges) → Turn the housing so that the filter element points downward after the instrument is installed. This provides better protection against buildup. VEGABAR 82 • Foundation Fieldbus...
  • Page 22: Process Pressure Measurement

    Instruments with absolute pressure have a blind plug mounted instead of the filter element. Process pressure measurement Measurement setup in Keep the following in mind when setting up the measuring system: gases • Mount the instrument above the measuring point Possible condensation can then drain off into the process line. VEGABAR 82 • Foundation Fieldbus...
  • Page 23 Pipeline Keep the following in mind when setting up the measuring system: Measurement setup in vapours • Connect via a siphon • Do not insulate the siphon • Fill the siphon with water before setup VEGABAR 82 • Foundation Fieldbus...
  • Page 24 < 100 °C on the transmitter is ensured. Measurement setup in Keep the following in mind when setting up the measuring system: liquids • Mount the instrument below the measuring point The effective pressure line is always filled with liquid and gas bubbles can bubble up to the process line. VEGABAR 82 • Foundation Fieldbus...
  • Page 25: Level Measurement

    Keep the following in mind when setting up the measuring system: • Mount the instrument below the min. level • Do not mount the instrument close to the filling stream or emptying area • Mount the instrument so that it is protected against pressure shocks from the stirrer Fig. 19: Measurement setup for level measurement VEGABAR 82 • Foundation Fieldbus...
  • Page 26: External Housing

    1. Mark the holes according to the following drilling template 2. Fasten wall mounting plate with 4 screws 90 mm (3.54") 70 mm (2.76") 8 mm (0.12") (0.32") Fig. 21: Drilling template - wall mounting plate VEGABAR 82 • Foundation Fieldbus...
  • Page 27: Connecting To The Bus System

    Max. torque for all housings, see chapter "Technical data". Cable screening and Make sure that the cable screen and grounding are carried out ac- grounding cording to Fieldbus specification. We recommend to connect the cable screen to ground potential on both ends. VEGABAR 82 • Foundation Fieldbus...
  • Page 28: Connecting

    1 cm (0.4 in) of insulation from the ends of the individual wires 5. Insert the cable into the sensor through the cable entry Fig. 22: Connection steps 5 and 6 - Single chamber housing VEGABAR 82 • Foundation Fieldbus...
  • Page 29: Single Chamber Housing

    10. Reinsert the display and adjustment module, if one was installed 11. Screw the housing lid back on The electrical connection is finished. Single chamber housing The following illustration applies to the non-Ex, Ex-ia and Ex-d ver- sion. VEGABAR 82 • Foundation Fieldbus...
  • Page 30: Double Chamber Housing

    6 7 8 Fig. 25: Electronics compartment - double chamber housing Internal connection to the terminal compartment Contact pins for the display and adjustment module or interface adapter Simulation switch ("1" = mode for simulation release) VEGABAR 82 • Foundation Fieldbus...
  • Page 31: Double Chamber Housing With Vegadis-Adapter

    VEGADIS adapter Internal plug connection Plug connector M12 x 1 Assignment of the plug connector Fig. 28: View to the plug connector M12 x 1 Pin 1 Pin 2 Pin 3 Pin 4 VEGABAR 82 • Foundation Fieldbus...
  • Page 32: Housing Ip 66/Ip 68 (1 Bar)

    Brown (+) and blue (-) to power supply or to the processing system Shielding External housing with version IP 68 (25 bar) Overview Fig. 30: VEGABAR 82 in IP 68 version 25 bar with axial cable outlet, external housing Transmitter Connection cable External housing VEGABAR 82 •...
  • Page 33: Power Supply

    Cable gland for voltage supply Cable gland for connection cable, transmitter Terminal compartment, housing socket 1 2 3 4 Fig. 32: Connection of the sensor in the housing base Yellow White Black Shielding Breather capillaries VEGABAR 82 • Foundation Fieldbus...
  • Page 34: Switch-On Phase

    Output signal at instruments with current output jumps to the set fault current Then the actual measured value is outputted to the signal cable. The value takes into account settings that have already been carried out, e.g. default setting. VEGABAR 82 • Foundation Fieldbus...
  • Page 35: Set Up With The Display And Adjustment Module

    The display and adjustment module is powered by the sensor, an ad- ditional connection is not necessary. Fig. 34: Installing the display and adjustment module in the electronics compart- ment of the single chamber housing VEGABAR 82 • Foundation Fieldbus...
  • Page 36: Adjustment System

    In the terminal compartment Note: If you intend to retrofit the instrument with a display and adjustment module for continuous measured value indication, a higher lid with an inspection glass is required. Adjustment system Fig. 36: Display and adjustment elements LC display Adjustment keys • Key functions [OK] key: VEGABAR 82 • Foundation Fieldbus...
  • Page 37 (with inspection window) of the sensor housing. Fig. 37: Display and adjustment elements - with adjustment via magnetic pen LC display Magnetic pen Adjustment keys Bluetooth symbol Lid with inspection window VEGABAR 82 • Foundation Fieldbus...
  • Page 38: Measured Value Indication

    Parameter adjustment - Quick setup To quickly and easily adapt the sensor to the application, select the menu item "Quick setup" in the start graphic on the display and adjustment module. Select the individual steps with the [->] key. VEGABAR 82 • Foundation Fieldbus...
  • Page 39: Parameter Adjustment - Extended Adjustment

    If possible, go through the items in the given sequence. The procedure is described below. The following submenu points are available: The submenu points are described below. VEGABAR 82 • Foundation Fieldbus...
  • Page 40 In this menu item you activate/deactivate the slave sensor for elec- Setup - Application tronic differential pressure and select the application. VEGABAR 82 can be used for process pressure and level measure- ment. Default setting is process pressure measurement. The mode can be changed in this adjustment menu.
  • Page 41 Setup - Adjustment VEGABAR 82 always measures pressure independently of the pro- cess variable selected in the menu item "Application". To output the selected process variable correctly, an allocation of the output signal to 0 % and 100 % must be carried out (adjustment).
  • Page 42 [OK]. Setup - Span adjustment Proceed as follows: 1. Select with [->] the menu item Span adjustment and confirm with [OK]. 2. Edit the mbar value with [OK] and set the cursor to the requested position with [->]. VEGABAR 82 • Foundation Fieldbus...
  • Page 43 3. Set the requested percentage value (e.g. 90 %) with [+] and save with [OK]. The cursor jumps now to the pressure value. 4. Enter the pressure value for the full vessel (e.g. 900 mbar) cor- responding to the percentage value. 5. Save settings with [OK] The max. adjustment is finished. VEGABAR 82 • Foundation Fieldbus...
  • Page 44 Releasing the sensor adjustment is also possible in any menu item by entering the PIN. Caution: With active PIN, adjustment via PACTware/DTM and other systems is also blocked. This menu item enables the setting of the requested national lan- Display - Language guage. VEGABAR 82 • Foundation Fieldbus...
  • Page 45 Chinese • Polish • Czech • Turkish In delivery status, the VEGABAR 82 is set to English. Display - Displayed value In this menu item, you define which measured value is displayed. 1 and 2 The default setting for the display value is "Lin. percent". Display - Display format In this menu item you define the number of decimal positions with 1 and 2 which the measured value is displayed.
  • Page 46 To deactivate the simulation, you have to push the [ESC] key and confirm the message "Deactivate simulation" with the [OK] key. Caution: During simulation, the simulated value is outputted as digital signal. The status message along with the Asset Management function is "Maintenance". VEGABAR 82 • Foundation Fieldbus...
  • Page 47 Unit of measurement mbar (with nominal measuring range ≤ 400 mbar) Units bar (with nominal measuring ranges ≥ 1 bar) Temperature unit °C Position correction 0.00 bar Adjustment Zero/Min. adjustment 0.00 bar 0.00 % Span/Max. adjustment Nominal measuring range in bar 100.00 % Damping Integration time Linearization Linear Lock adjustment Released VEGABAR 82 • Foundation Fieldbus...
  • Page 48: Instrument Settings

    The following data or settings for adjustment of the display and ad- justment module are saved: • All data of the menu "Setup" and "Display" • In the menu "Additional adjustments" the items "Reset, Date/Time" • The user-programmable linearization curve VEGABAR 82 • Foundation Fieldbus...
  • Page 49 In this menu item, the date of factory calibration of the sensor as well Info - Factory calibration date as the date of the last change of sensor parameters are displayed via the display and adjustment module or via the PC. VEGABAR 82 • Foundation Fieldbus...
  • Page 50: Saving The Parameterisation Data

    If it is necessary to exchange a sensor, the display and adjustment module is inserted into the replacement instrument and the data are likewise written into the sensor via the menu item "Copy device settings". VEGABAR 82 • Foundation Fieldbus...
  • Page 51: Setup With Pactware

    Further setup steps are described in the operating instructions manu- al "DTM Collection/PACTware" attached to each DTM Collection and which can also be downloaded from the Internet. Detailed descrip- tions are available in the online help of PACTware and the DTMs. VEGABAR 82 • Foundation Fieldbus...
  • Page 52: Saving The Parameterisation Data

    The standard version is available as a download under www.vega.com/downloads and "Software". The full version is avail- able on CD from the agency serving you. Saving the parameterisation data We recommend documenting or saving the parameterisation data via PACTware.
  • Page 53: Set Up With Other Systems

    8 Set up with other systems Set up with other systems DD adjustment programs Device descriptions as Enhanced Device Description (EDD) are available for DD adjustment programs such as, for example, AMS™ and PDM. The files can be downloaded at www.vega.com/downloads under "Software". VEGABAR 82 • Foundation Fieldbus...
  • Page 54: Diagnosis, Asset Management And Service

    Overview The hygienic connection with compression nut can be disassembled and the diaphragm cleaned. The following graphic shows the structure: Fig. 41: VEGABAR 82, structure of the hygienic connection with compression Hexagon Compression nut Process fitting Process module...
  • Page 55: Diagnosis Memory

    EDD. Asset Management function The instrument features self-monitoring and diagnostics according to NE 107 and VDI/VDE 2650. In addition to the status messages in the following tables, detailed error messages are available under menu VEGABAR 82 • Foundation Fieldbus...
  • Page 56 Code Cause Rectification DevSpec Text message Diagnosis Bits • • F013 Gauge pressure or low pressure Exchange measuring cell Bit 0 • • Measuring cell defective Send instrument for repair No valid measured value available VEGABAR 82 • Foundation Fieldbus...
  • Page 57 • Invalid sensor configuration (e.g.: application electronic differential pressure with con- nected differential pressure measuring cell) • • F265 Sensor no longer carries out a Carry out a reset Bit 11 • measurement Disconnect operating voltage Measurement func- briefly tion disturbed VEGABAR 82 • Foundation Fieldbus...
  • Page 58 Send instrument for repair Error at a device in- terface • • M507 Error during setup Carry out reset and repeat Bit 22 • Error when carrying out a reset setup Error in the instru- ment settings VEGABAR 82 • Foundation Fieldbus...
  • Page 59: Rectify Faults

    24 hour service hotline Should these measures not be successful, please call in urgent cases the VEGA service hotline under the phone no. +49 1805 858550. The hotline is also available outside normal working hours, seven days a week around the clock.
  • Page 60: Exchanging The Electronics Module

    9 Diagnosis, asset management and service Fig. 43: VEGABAR 82 in IP 68 version, 25 bar and lateral cable outlet, external housing Process module Plug connector Fixing screw Cable assembly Connection cable External housing 3. Loosen the plug connector 4. Mount the new process module on the measuring point 5.
  • Page 61: Software Update

    Clean the instrument and pack it damage-proof • Attach the completed form and, if need be, also a safety data sheet outside on the packaging • Please contact the agency serving you to get the address for the return shipment. You can find the agency on our home page www.vega.com. VEGABAR 82 • Foundation Fieldbus...
  • Page 62: Dismount

    Pass the instrument directly on to a spe- cialised recycling company and do not use the municipal collecting points. These may be used only for privately used products according to the WEEE directive. VEGABAR 82 • Foundation Fieldbus...
  • Page 63: Supplement

    Ʋ Sealing, cable gland Ʋ Blind plug, cable gland Ʋ Seal between housing and housing lid Silicone SI 850 R, NBR silicone-free Ʋ Inspection window in housing cover Polycarbonate, UL746-C listed (with Ex-d version: glass) VEGABAR 82 • Foundation Fieldbus...
  • Page 64 Ʋ Type label support on cable PE hard Connection cable with IP 68 (1 bar) PE, PUR version Weights Total weight VEGABAR 82 approx. 0.8 … 8 kg (1.764 … 17.64 lbs), depending on process fitting and housing Torques Max. torque for process fitting Ʋ G½, G¾...
  • Page 65 0 … +100 bar/0 … +10000 kPa 200 bar/20000 kPa 0 bar abs. (only for measuring cell ø 28 mm) Nominal measuring ranges and overload capacity in psi Nominal range Overload capacity, max. pressure Overload capacity, min. pressure Gauge pressure VEGABAR 82 • Foundation Fieldbus...
  • Page 66 0 psi 0 … 300 psi 1500 psi 0 psi 0 … 900 psi +2900 psig 0 psi 0 … +1450 psig 2900 psig 0 psi (only for measuring cell ø 28 mm) Adjustment ranges Specifications refer to the nominal measuring range, pressure values lower than -1 bar cannot be VEGABAR 82 • Foundation Fieldbus...
  • Page 67 : dead time; t : rise time; t : jump response time Process variable Output signal VEGABAR 82 VEGABAR 82 - IP 68 (25 bar) Dead time ≤ 25 ms ≤ 50 ms Rise time (10 … 90 %) ≤ 55 ms ≤ 150 ms VEGABAR 82 • Foundation Fieldbus...
  • Page 68 11 Supplement VEGABAR 82 VEGABAR 82 - IP 68 (25 bar) Step response time (ti: 0 s, 10 … 90 %) ≤ 80 ms ≤ 200 ms Damping (63 % of the input variable) 0 … 999 s, adjustable via menu item "Damping" Additional output parameter - Measuring cell temperature Detection area -60 …...
  • Page 69 In the table, example values for typical Turn downs are listed. Turn Down TD 1 : 1 TD 2.5 : 1 TD 5 : 1 TD 10 : 1 TD 20 : 1 Factor FTD 1.75 10.5 VEGABAR 82 • Foundation Fieldbus...
  • Page 70: Ambient Conditions

    -20 … +80 °C (-4 … +176 °F) -20 … +80 °C (-4 … +176 °F) Version IP 68 (25 bar) with connec- -20 … +80 °C (-4 … +176 °F) -20 … +80 °C (-4 … +176 °F) tion cable PUR VEGABAR 82 • Foundation Fieldbus...
  • Page 71 (32 °F) 100 °C 130 °C -40 °C (212 °F) (266 °F) (-104 °F) -40 °C (-104 °F) Fig. 46: Temperature derating VEGABAR 82, version up to +130 °C (+266 °F) Process temperature Ambient temperature With process fitting PVDF, process temperature max. 100 °C (212 °F). VEGABAR 82 • Foundation Fieldbus...
  • Page 72 -40 °C (212 °F) (302 °F) (-104 °F) -40 °C (-104 °F) Fig. 47: Temperature derating VEGABAR 82, version up to +150 °C (+302 °F) Process temperature Ambient temperature SIP process temperature (SIP = Sterilization in place) Applies to instruments configurations suitable for vapour, i.e. material measuring cell seal EPDM or FFKM (Perlast G75S).
  • Page 73 Ʋ Number of digits Ʋ Size of digits W x H = 7 x 13 mm Adjustment elements Ʋ 4 keys [OK], [->], [+], [ESC] Ʋ Switch Bluetooth On/Off Bluetooth interface Ʋ Standard Bluetooth smart Breather capillaries not with Ex-d version. VEGABAR 82 • Foundation Fieldbus...
  • Page 74 Ʋ Analogue Via the current output Ʋ Digital Via the digital output signal (depending on the electron- ics version) Range -40 … +85 °C (-40 … +185 °F) Resolution < 0.1 K Accuracy ±3 K VEGABAR 82 • Foundation Fieldbus...
  • Page 75 Stainless steel Transmitter, version with IP 68 (25 bar) external housing Connection of the feeding power supply Networks of overvoltage category III unit Protection rating IP 66/IP 68 (0.2 bar) only in conjunction with absolute pressure. VEGABAR 82 • Foundation Fieldbus...
  • Page 76: Supplementary Information Foundation Fieldbus

    Instruments with approvals can have different technical specifications depending on the version. For that reason the associated approval documents of these instruments have to be carefully noted. They are part of the delivery or can be downloaded under www.vega.com, "Instrument search (serial number)" as well as in the download area. 11.2 Supplementary information Foundation Fieldbus The following table gives you an overview of the instrument versions and the corresponding device descriptions, the electrical characteristics of the bus system as well as the applied function blocks.
  • Page 77 Fig. 48: Schematic presentation Transducer Block (TB) Function block Analog Input (AI) The function block "Analog Input (AI)" takes the original measured value selected by a Channel Number and makes it available to additional function blocks on its output. VEGABAR 82 • Foundation Fieldbus...
  • Page 78 The function block "PID Control " is a key component for various tasks in the process automation and is used universally. PID blocks can be cascaded if this is necessary or requested due to differ- ent time constants with the primary and secondary process measurement. Fig. 51: Schematic presentation function block PID Control VEGABAR 82 • Foundation Fieldbus...
  • Page 79 The function block "Integrator" integrates a continuous input signal over the time and sums the results of an impulse input block. It is used as a totalizer up to a reset or as a subtotalizer up to a reference point at which the integrated and accumulated value is compared with the default values. When these default values are reached, digital output signals will be outputted. The integration func- tion is carried out upwardly starting with zero and downwards with a default value. Two flow values are also available so that the net flow volume can be calculated and integrated. This can be used for calculation of volume and mass changes in the vessel or for optimisation of flow controls. VEGABAR 82 • Foundation Fieldbus...
  • Page 80 The function block "Arithmetic" allows the simple integration of usual metrological calculation func- tions. The user can select the requested measurement algortihm according to the name without known the formula. The following algorithms are available: • Flow compensation, linear • Flow compensation, square root VEGABAR 82 • Foundation Fieldbus...
  • Page 81: Calculation Of The Total Deviation

    + (F perf To provide a better overview, the formula symbols are listed together below: • : Total deviation total • : Basic accuracy perf • : Long-term stability • stab : Thermal change of zero signal and output span (temperature error) • : Deviation VEGABAR 82 • Foundation Fieldbus...
  • Page 82: Practical Example

    TBasis = 0.15 % x 3 x 1.75 = 0.79 % 3. Determination of deviation and long-term stability The required values for deviation F and long-term stability F are available in the technical data: stab VEGABAR 82 • Foundation Fieldbus...
  • Page 83: Dimensions

    The example shows that the measurement error in practice can be considerably higher than the basic accuracy. Reasons are temperature influence and Turn down. 11.5 Dimensions The following dimensional drawings represent only an extract of the possible versions. Detailed dimensional drawings can be downloaded at www.vega.com under "Downloads" and "Drawings". VEGABAR 82 • Foundation Fieldbus...
  • Page 84 ½ NPT Fig. 59: Housing versions with protection rating IP 66/IP 68 (0.2 bar) - with integrated display and adjustment module the housing is 9 mm/0.35 in higher Aluminium - single chamber Aluminium - double chamber VEGABAR 82 • Foundation Fieldbus...
  • Page 85 Fig. 61: Housing versions with protection rating IP 66/IP 68 (0.2 bar) - with integrated display and adjustment module the housing is 9 mm/0.35 in higher Stainless steel single chamber (electropolished) Stainless steel single chamber (precision casting) Stainless steel double chamber housing (precision casting) VEGABAR 82 • Foundation Fieldbus...
  • Page 86 ø 80 mm (3.15") M20x1,5/ ½ NPT Fig. 63: Housing version with protection rating IP 69K - with integrated display and adjustment module the housing is 9 mm/0.35 in higher Stainless steel single chamber (electropolished) VEGABAR 82 • Foundation Fieldbus...
  • Page 87 (1.64") ~ 66 mm (2.60") 110 mm x 90 mm (4.33" x 3.54") Fig. 64: VEGABAR 82, IP 68 version with external housing Lateral cable outlet Axial cable outlet Plastic single chamber Stainless steel single chamber Seal 2 mm (0.079 in), (only with 3A approval)
  • Page 88 ø 6 mm ø 6 mm ( 0.24 ") ( 0.24 ") Fig. 65: VEGABAR 82, threaded fitting not front-flush DU G½, EN 837; manometer connection DI G½, inside G¼ A, ISO 228-1 DQ G½, inside G¼ A, ISO 228-1 DD G½, EN 837;...
  • Page 89 ø 55 mm ø 55 mm ø 60 mm (2.17") (2.17") (2.36") Fig. 66: VEGABAR 82, threaded fitting front-flush C3 G½, ISO 228-1; front-flush N9 G¾, DIN 3852-E C5 G1, ISO 228-1 DA G1½, DIN 3852-A DV G1½, DIN 3852-A-B, PVDF C9 1½...
  • Page 90 (3.31") ø 92 mm (3.62") (3.62") EZ/NB Fig. 67: VEGABAR 82, hygienic fitting AR Clamp 2" PN 16 (ø 64 mm) DIN 32676, ISO 2852 ES Hygienic connection with compression nut F40 PN 25 AA DRD PN 40 FR Varivent N50-40 PN 25...
  • Page 91 0.94 " 6 " 8xø 0.75 " 5” Fig. 68: VEGABAR 82, flange connection Flange connection according to DIN 2501 Flange connection according to ASME B16.5 F7 Flange DN 50 PN 40 Form C, DIN 2501; with extension F2 Flange DN 80 PN 40 Form C, DIN 2501; with extension Notes: - For the version with temperature range up to 150 °C/302 °F, the measure of length increases by...
  • Page 92 ø 48 mm (1.04") (1.89") ø 85 mm (3.35") Fig. 69: VEGABAR 82, extension fitting AL/AP M30 x 1.5 DIN 13; completely front-flush/for headbox AF/AG M44 x 1.25 DIN 13; pressure screw: Aluminium/316L F9 G1, ISO 228-1 suitable for PASVE EW PMC 1"...
  • Page 93 (1.89") 115 mm (4.53") ø 48 mm (1.89") 50 mm 50 mm (1.97") (1.97") Fig. 70: VEGABAR 82, extension fitting for headbox CL Completely front-flush for headbox BR Completely front-flush for headbox (flange 2-times flattened) VEGABAR 82 • Foundation Fieldbus...
  • Page 94 41 mm (1.63") 65 mm (2.56") Fig. 71: VEGABAR 82, connection acc. to IEC 61518 SJ Oval flange adapter SK Top flange Notes: For the version with temperature range up to 150 °C/302 °F, the measure of length increases by 28 mm (1.1 in).
  • Page 95: Industrial Property Rights

    Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellec- tuelle. Pour plus d'informations, on pourra se référer au site www.vega.com. VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad indus- trial. Para mayor información revise la pagina web www.vega.com.
  • Page 96 – Integrator 79 – Output Splitter 79 – PID Control 78 – Signal Characterizer 79 – Transducer Block (TB) 77 Linearisation 44 Maintenance 54 Measured value memory 55 Measurement setup 22, 23, 24, 25 NAMUR NE 107 55 VEGABAR 82 • Foundation Fieldbus...
  • Page 97 Notes VEGABAR 82 • Foundation Fieldbus...
  • Page 98 Notes VEGABAR 82 • Foundation Fieldbus...
  • Page 99 Notes VEGABAR 82 • Foundation Fieldbus...
  • Page 100 Subject to change without prior notice © VEGA Grieshaber KG, Schiltach/Germany 2017 VEGA Grieshaber KG Phone +49 7836 50-0 Am Hohenstein 113...