Ups Configuration - Riello 100 kVA Manual

Uninterruptible power supply system
Table of Contents

Advertisement

UPS
CONFIGURATION
The table below illustrates all the possible configurations available to the user in order to best adapt the UPS to individual
requirements.
CP
(Control Panel)
SW
(Software)
FUNCTION
Output frequency
Output voltage
Operating mode
Power-off due to
minimum charge
Autonomy limit
Battery low
warning
Battery test
Maximum load
alarm threshold
Audible alarm
Auxiliary socket
(power share)
Battery box
capacity
Language**
Indicates that the configuration can be modified from the control panel as well as from the
configuration software.
Indicates that the configuration can be only be modified using the configuration software.
DESCRIPTION
Selects the rated output
frequency
(in order for the setting to
become active, it is
necessary to switch the UPS
off and back on again)
Selects the rated output
voltage
(Phase - Neutral)
Selects one of five different
operating modes
Automatic UPS power-off in
battery operation mode if the
charge is lower than 5%
Maximum battery operation
time
Estimated autonomy time
remaining for the battery low
warning
Interval of time for the
automatic battery test
Selects the user overload
limit
Selects the audible alarm
operating mode
Selects the auxiliary socket
operating mode
Sets the Ah installed
Selects the language
DEFAULT
POSSIBLE CONFIGURATIONS
 50 Hz
50 Hz
 60 Hz
 200V *
 208V *
 220V
230V
 230V
 240V
 220 - 240 in 1V stages
(from software only)
 ON LINE
 ECO
 SMART ACTIVE
ON LINE
 STAND-BY OFF
 FREQUENCY CONVERTER
(from software only)
 Enabled
Disabled
 Disabled
 Disabled (complete battery
Disabled
discharge)
 1 - 65000 in 1 sec stages
3 min.
1 - 255 in min stages
 Disabled
40 ore
 1 - 1000 in 1 hour stages
 Disabled
Disabled
 0 - 103 in 1% stages
 Normal
 Reduced: does not sound due to
Reduced
the momentary intervention of the
bypass
 Always connected
 Disconnection after n seconds of
battery operation
Always
 Disconnection after n seconds
connected
from the battery low pre-alarm
signal
 ... (see UPSTools manual)
Min.: 0 - Max.: 999
0 Ah
(in 1 unit stages)
 English
 Italian
English
 German
 French
MODEL
CP
CP
CP
CP
SW
SW
SW
SW
CP
SW
CP
 Spanish
 Polish
CP
 Turkish
 Chinese