Ups Configuration - Riello Dialog Plus DLP series User Manual

700-3000 va
Table of Contents

Advertisement

I
NSTALLATION AND
UPS C
ONFIGURATION
The following table lists all the possible configurations available so as to best adapt the UPS to user
requirements. The configuration may be modified only by using the configuration software provided.
FUNCTION
Automatic Restart
Remaining battery charge
Battery low alarm
Allows the user to select
Output frequency
Allows the user to select
Output voltage
Selects the voltage range
Bypass voltage
threshold
Allow the user to set the
Battery capacity
0MNUOC1RUA_GB (614-06498-00)
U
SE
DESCRIPTION
Automatic restart when
mains power returns
level setting for the
battery low alarm
the output frequency.
the output voltage
accepted for switching
over to bypass
capacity of battery
PREDEFINED
• Disabled
Enabled.
• Enabled
3 min.
1 - 99 in steps of 1 minute
• 50Hz
• 60Hz
50Hz
• Auto (depending on the UPS input frequency
• 220 Vac
• 230 Vac
230 Vac
• 240 Vac
Low:
180V
Low: 180 ÷ 200 in steps of 1V
High: 264V
High: 250 ÷ 264 in steps of 1V
The user must set the capacity of battery if the
Standard: 7.2Ah
actual capacity is different from the default
ER:
65Ah
value.
POSSIBLE CONFIGURATIONS
it will operate at 50 or 60 Hz)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents