Separate Bypass On Separate Lines; Ups Connected To An Independent Power Line; Ups With Separate Bypass Input Connected To Independent Power Line - Riello 100 kVA Manual

Uninterruptible power supply system
Table of Contents

Advertisement

Separate bypass on separate lines:

N.B. the input line neutral and the bypass neutral are joined inside the equipment, therefore they must be referred to the
same potential. If the two power supply sources are different, is it necessary to use an isolating transformer on one of the
inputs.
UPS without variation of the neutral point treatment and with separate bypass input
Remove the jumpers present between the SWIN and SWBY isolating switches
Remove the jumpers present between the SWIN and SWBY isolating switches
Remove the jumpers present between the SWIN and SWBY isolating switches
connected to an independent power line
UPS with separate bypass input connected to an independent
power line and with input galvanic isolation
UPS with separate bypass input connected to an independent
power line and with output galvanic isolation