Riello 100 kVA Manual page 32

Uninterruptible power supply system
Table of Contents

Advertisement

FUNCTION
Input frequency
tolerance range
Bypass voltage
thresholds
Bypass voltage
thresholds for
ECO
Intervention
sensitivity for ECO
Load feeding in
stand-by
Bypass
operation
Inverter
synchronisation
(External Sync)
Switch-on delay
Power Walk-In
Power Walk-In
Duration
Inverter
synchronisation
speed to bypass
line
External
temperature probe
(optional)
UPS settings from
the display
UPS commands
from the display
* Setting these output voltage values will lead to the reduction of the output power of the UPS (see "Reducing the load
(at 200V and 208V) paragraph")
** Pressing the F1 and F4 keys at the same time for t > 2 sec will automatically reset English as the language.
DESCRIPTION
Advanced Functions
Selects the accepted range
for the input frequency for
switching to the bypass and
for the synchronisation of the
output
Selects the accepted voltage
range for switching to the
bypass
Selects the accepted voltage
range for operation in ECO
mode
Selects the intervention
sensitivity during operation in
ECO mode
Load feeding on bypass with
UPS off (stand-by mode)
Selects the mode of use of
the bypass line
Selects the source of
synchronisation for the
inverter output
Waiting time for automatic
power-on after the return of
mains voltage
Activates the gradual return
to mains voltage mode
Sets the duration of the
gradual return to mains
voltage (only if Power Walk-
In is activated)
Selects the synchronisation
speed of the inverter to the
bypass line
Activates reading of the
external temperature probe
Disables UPS settings from
the Display Panel
Disables the sending of
commands from the Display
Panel
DEFAULT
POSSIBLE CONFIGURATIONS
 ± 0.25%
 ± 0.5%
± 5%
 ± 0.75%
 ± 1 - ±10 in 1% stages
Low: 180V
Low: 180 - 200 in 1V stages
High: 264V
High: 250 - 264 in 1V stages
Low: 200V
Low: 180 - 220 in 1V stages
High: 253V
High: 240 - 264 in 1V stages
 Low
 Normal
Normal
 High
Disabled
 Disabled (not powered)
(load NOT
 Enabled (powered)
powered)
 Enabled / High sensitivity
 Enabled / Low sensitivity
Enabled /
 Disabled with input/output
High
synchronisation
sensitivity
 Disabled without input/output
synchronisation
 From bypass line
From bypass
 From external input
line
 Disabled
5 sec.
 1 - 255 in 1 sec stages.
 Activated
Deactivated
 Deactivated
10 sec
Min.: 1 sec. - Max.: 30 sec.
 0.5 Hz/sec
 1 Hz/sec
1 Hz/sec
 1.5 Hz/sec
 2 Hz/sec
 Not activated
Not activated
 Activated
 Settings enabled
Settings
 Settings disabled
enabled
 Commands enabled
Commands
 Commands disabled
enabled
MODEL
SW
SW
SW
CP
SW
SW
SW
CP
SW
SW
SW
SW
SW
SW