- ON LINE RACK -
Modelli / Models / Modelle / Modèles / Modelos
700 VA ÷ 3000 VA
Manuale d'uso / User's manual / Bedienungsanleitung /
Manuel d'utilisateur / Manual de usuario

Advertisement

Table of Contents
loading

Summary of Contents for Riello 700VA

  • Page 1 NINTERRUPTIBLE OWER UPPLY - ON LINE RACK - Modelli / Models / Modelle / Modèles / Modelos 700 VA ÷ 3000 VA Manuale d’uso / User’s manual / Bedienungsanleitung / Manuel d’utilisateur / Manual de usuario...
  • Page 3 SAFETY This part of the manual contains precautions that must absolutely be followed as they relate to SAFETY. Installation Connect the UPS system only to an earthed shockproof socket outlet. The building wiring socket outlet (shockproof socket outlet) must be easily accessible and close to the UPS system.
  • Page 4 USER’S MANUAL...
  • Page 5 NTRODUCTION Thanks you for choosing our product. Our manufacturer are renowned specialists in the development and production of uninterruptible power supplies (UPS). The UPS in this range are high quality products, designed and built with care in order to give you the best performance.
  • Page 6: Table Of Contents

    ONTENTS RESENTATION IEW OF THE Front Views Rear Views IEW OF LED INDICATOR PANEL NSTALLATION AND PENING THE PACKAGING AND CHECKING THE CONTENTS NSTALLATION OF HANDLES ONNECTIONS AND FIRST START WITCHING ON FROM MAINS POWER TART UP FROM BATTERY SHUTDOWN ED INDICATOR PANEL VERLOADS ON THE OMMUNICATION PORTS...
  • Page 7: Presentation

    XL:without batteries inside, but including a powerful batterycharger (max 8A). This series must be combined with an external battery box, so it is indicated for long autonomy time. The figures below show the various product versions: 1000VA / 2200VA / 3000VA / 700VA 1500VA 1000VA XL 2200VA XL 3000VA XL Nominal power...
  • Page 8: View Of The Ups

    RESENTATION IEW OF THE Front Views 700VA / 1000VA / 1000VA XL / 1500VA 2200VA / 2200VA XL / 3000VA / 3000VA XL BATTERY BOX (included in 2200VA / 3000VA models) FUSE 25A GL 400V 1. LED indicator panel 2. ON button 3.
  • Page 9: Rear Views

    RESENTATION Rear Views 700VA 1000VA / 1000VA XL 1500VA 2200VA...
  • Page 10 RESENTATION 2200VA XL 3000VA / 3000VA XL BATTERY BOX 1. RS232 serial communication port 5. IEC mains input plug 2. Cooling fan 6. Battery expansion socket 3. IEC output sockets (max 10A) 7. IEC 16A output socket 4. Input thermal protection...
  • Page 11: View Of Led Indicator Panel

    RESENTATION IEW OF LED INDICATOR PANEL LOAD Load level indicator Battery level indicator Mains mode indicator Battery mode indicator / Battery low indicator Battery failure indicator Load powered by bypass indicator “Fault/Stand-by” indicator...
  • Page 12: Installation And Use

    NSTALLATION AND PENING THE PACKAGING AND CHECKING THE CONTENTS The first thing to do after opening the packaging is to check the contents The packaging should contain the following: IEC 16A loose plug (only for 3000VA / 3000VA XL) IEC 10A (or 16A) power supply cable Battery expansion connector (only for XL models) 2 IEC-IEC 10A connection cables...
  • Page 13: Installation Of Handles

    NSTALLATION AND USE This chapter describes the operations to be carried out to prepare the UPS. WARNING: the instructions below should be followed scrupulously for your personal safety and that of the product. BEFORE CARRYING OUT THE FOLLOWING SEQUENCE OF OPERATIONS, MAKE SURE THAT THE UPS IS COMPLETELY SWITCHED OFF AND IS NOT CONNECTED TO THE MAINS OR TO ANY LOAD.
  • Page 14: Start - Up From Battery

    NSTALLATION AND USE TART UP FROM BATTERY 1) With mains not present, press the “ON” button for approx. 1 second (until a beep is heard) and then release. All the display LEDs will light up for 1 second and the UPS will emit a beep. The battery voltage is checked and if all is normal, only the battery operation, the load bar and the battery bar LEDs remain lit, accompanied by an intermittent beep.
  • Page 15: Led Indicator Panel

    NSTALLATION AND ED INDICATOR PANEL This chapter gives a detailed description of all LED indicator panel. ICON STATUS DESCRIPTION Red / Steady Indicates an fault Red / The UPS is in stand-by mode Flashing Green / Steady The UPS is operating on mains power The UPS is operating off the bypass Green / Flashing The voltage input is out of the accepted range...
  • Page 16: Overloads On The Ups

    NSTALLATION AND Table 1 Battery LED bar Battery level 0%~20% ● 20%~40% ● ● 40%~60% ● ● ● 60%~80% ● ● ● ● 80%~100% ● ● ● ● ● Table 2 Battery LED bar Input Voltage 190V~200V ● 200V~230V ● ●...
  • Page 17: Communication Ports

    NSTALLATION AND After switching over to the bypass due to overloading, the UPS powers the loads off mains power and a continuous alarm will sound. By reducing the load within the 102% threshold, the UPS returns to normal operating mode. When the overload level is too high, the input thermal protection is activated and the UPS will be completely shutdown.
  • Page 18: Communication Slot

    NSTALLATION AND Communication Slot All UPS come with an expansion slot for optional communication boards so that the unit is compatible with the main communication standards. Some examples: • Serial port duplexer • Ethernet network agent with TCP/IP, HTTP and SNMP protocols •...
  • Page 19: Ups Configuration

    NSTALLATION AND UPS C ONFIGURATION The following table lists all the possible configurations available so as to best adapt the UPS to user requirements. The configuration may be modified only by using the configuration software provided (UPSTools). FUNCTION DESCRIPTION PREDEFINED POSSIBLE CONFIGURATIONS •...
  • Page 20: Alarms And Indicators

    LARMS AND NDICATORS STATUS REPORTS TABLE The following table describes the light and audio indicators that appear/sound during normal UPS operation. Load level Battery level Battery Failure/ Mains Battery Audio UPS Status pass failure Fault Alarm ♦ Standby ♦ Bypass Load level Battery level ●...
  • Page 21: Ups Failure Reports Table

    LARMS AND INDICATORS FAILURE REPORTS TABLE The following table describes the light and audio signals that appear/sound to indicate a fault. Load level Battery level Battery Failure/ Mains Battery Bypass Audio UPS Status failure Fault Alarm 1 2 3 4 5 1 2 beeps Alarm phase ●...
  • Page 22: Roblem Solving

    ROBLEM SOLVING Very often incorrect UPS operation is not caused by a fault but by common problems, difficulties or carelessness. The table below gives some useful information to help the user solve the most frequent problems. PROBLEM POSSIBLE CAUSE SOLUTION THE POWER CABLE IS NOT Check that the power cable is connected correctly.
  • Page 23: Technical Specifications

    ECHNICAL PECIFICATIONS MODELS 700VA 1000VA 1000VA XL INPUT Nominal voltage [Vac] 220 / 230 / 240 Transfer Voltage Range - low line transfer [load %] Based on load percentage [Vac] 100-80% =160 ± 5 80-70% = 140 ± 5 70-60%= 120 ± 5 60-0%= 110 ±...
  • Page 24 ECHNICAL SPECIFICATIONS MODELS 1500VA 2200VA 2200VA XL INPUT Nominal Voltage [Vac] 220 / 230 / 240 Transfer Voltage Range -Low line transfer [load %] Based on load percentage [Vac] 100-80% =160 ± 5 80-70% = 140 ± 5 70-60%= 120 ± 5 60-0%= 110 ±...
  • Page 25 ECHNICAL PECIFICATIONS MODELS 3000VA 3000VA XL INPUT Nominal voltage [Vac] 220 / 230 / 240 Transfer Voltage Range -Low line transfer [load %] Based on load percentage [Vac] 100-80% =160 ± 5 80-70% = 140 ± 5 70-60%= 120 ± 5 60-0%= 110 ±...
  • Page 26 ECHNICAL SPECIFICATIONS at nominal load, minimum voltage of 164 Vac, battery charging at nominal load, nominal voltage of 230Vac, battery charging Second appendix M5 of the EN50091-1-1 specifications Mains/Battery at load: 0% -100% at Mains / battery / mains at resistive load: 0% / 100% / 0% If the mains frequency falls within ±...
  • Page 27 0MNUC2RNPA...