Riello 100 kVA Manual page 45

Uninterruptible power supply system
Table of Contents

Advertisement

Battery charger stage
Rated voltage
Maximum recharging current
Battery charger algorithm
Technology
Input voltage tolerance range for recharging at
maximum current
UPS models
Dimensions and weights
Width x Depth x Height
Type of structural work
Weight (without batteries)
Modes and levels of efficiency
Operating modes
AC/AC efficiency in on line mode
AC/AC efficiency in Eco mode
Maximum power dissipation
Environment of installation
Max relative humidty during operation
Max installation height
Fan flow rate in place of installation to disperse
(9)
heat
Protection rating
Cable entry
Other
Noise level
Colour
(7)
Ambient temperature
(1)
In order to ensure the output voltage remains within the range of precision shown, it may be necessary to recalibrate after a long
period of operation
(2)
If the mains frequency is within ± 5% of the selected value, the UPS is synchronised with the mains. If the frequency is outside the
tolerance range or in battery operation mode, the frequency is as selected +0.1%
(3)
Mains/Battery @ load 0% -100%
(4)
@ Mains / battery / main @ resistive load 0% / 100% / 0%
(5)
The recharging current is regulated automatically in the basis of the capacity of the battery installed
(6)
The "-" symbol replaces an alphanumerical code for internal use
(7)
20 – 25 °C for longer battery life
(8)
@ 100% load & THDv ≤ 1%
(9)
The table shows an example of the flow rate (at - et)=5°C and with resistive rated load (pf=0.9)
(5)
Tower type with wheels, movement with transpallet, display fixed to the top of the
door. Door at the top for access to switches and connections
240Vdc
Two levels with temperature compensation
Analogue switching current mode under the control of the P
(PWM regulation of charging current and voltage)
345-480Vac
100 kVA
750 x 855 x 1900 mm
370 kg
True on line double conversion
ECO mode
Smart Active mode
Stand-by Off (Emergency power supply)
Frequency Converter
94%
6900 W
90 % (without condensation)
1000 m at rated power
(-1% power for every 100 m above 1000 m)
max 4000 m
3600 mc³/h
back/front
≤70dB(A)
RAL 7016
0 – 40 °C
25A
120 kVA
380 kg
94%
98%
7200 W
3800 m³/h
IP20
≤70dB(A)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

120 kvaMulti plus mlt100Multi plus mlt120

Table of Contents