UPS models
Input stage
Rated voltage
Nominal voltage
Max input current
Max battery current
Accepted input tolerance range in order to
prevent battery intervention (refers to 400Vac)
Accepted input tolerance range in order to
prevent battery intervention (refers to 50/60Hz)
Technology
Input current harmonic distortion
Input power factor
Power Walk-In
Output stage
(1)
Rated voltage
(2)
Nominal voltage
Output current
Rated apparent output power
Rated active output power
Output power factor
Short circuit current
Output voltage precision (refers to 400Vac
output voltage)
(3)
Static stability
Dynamic stability
Output voltage harmonic distortion with
standardised linear and distorting load
Crest factor allowed at rated load
Frequency precision in free running mode
Inverter overloads @ PF =0.9 (resistive load)
Inverter overloads @ PF =0.8 (resistive load)
Bypass overloads
Technology

TECHNICAL DATA

100 kVA
380-400-415 Vac three-phase with neutral (4 wire)
185 A
254 A
IGBT high frequency with PFC control, independent digital average current mode
Can be programmed from 5 to 30 sec in 1 sec stages.
380/400/415 Vac three-phase with neutral (4 wire)
152 A
100kVA
90kW
IGBT high frequency with multiprocessor digital control (DSP+P)
50-60Hz
20% @ 100% load
-40% +20% @50% load
20%
40-72Hz
on each input phase
(8)
THDi  4 %
≥0.99
50/60Hz
0.9
1.5x Ir for t>500ms
 1%
 0.5%
 3% resistive load
2% with linear load
4% with distorting load
3:1
0.01%
103-110% 10 minutes @ Vin>345Vac
110-133% 1 minutes @ Vin>345Vac
133-150% 5 sec @ Vin>345Vac
>150% 0.5 sec @ Vin>345Vac
103-115% infinite @ Vin>345Vac
115-125% 10 minutes @ Vin>345Vac
125-150% 1 minute @ Vin>345Vac
150-168% 5 sec @ Vin>345Vac
>168% 0.5 sec @ Vin>345Vac
<110% infinite
110-125% 60 minutes
125-150% 1 minute
120 kVA
216 A
304 A
182 A
120kVA
108kW