2.13.6 Operate and Reset Time (59NIT)
Attribute
t
Starter operate time (≥ 2xVs)
basic
char = IDMTL
Operate
t
op
time
char = DTL
char = IDMTL
Reset Time
char = DTL
Repeatability
Overshoot time
Disengaging time
©2010 Siemens Protection Devices Limited
7SR224 Argus Performance Specification
Value
65 ms, ± 20ms
M
=
t
, ± 5 % or ± 65 ms
[ ]
op
−
3
V
0
1
Vs
, ± 1 % or ± 40ms
t
d
, ± 5 % or ± 65ms
t
res
, ± 1 % or ± 40ms
t
res
± 1 % or ± 20ms
< 40 ms
< 50 ms
Chapter 3 Page 37 of 49