Figure 2.8-1 Binary Input Logic - Siemens 7SR224 Technical Manual

Recloser controller
Hide thumbs Also See for 7SR224:
Table of Contents

Advertisement

Pick-up (PU) and drop-off (DO) time delays are associated with each binary input. Where no pick-up time delay
has been applied the input may pick up due to induced ac voltage on the wiring connections (e.g. cross site
wiring). The default pick-up time of 20ms provides ac immunity. Each input can be programmed independently.
Each input may be logically inverted to facilitate integration of the relay within the user scheme. When inverted the
relay indicates that the BI is energised when no d.c. is applied. Inversion occurs before the PU & DO time delay,
see fig. 2.8-1.
Each input may be mapped to any front Fascia indication LED and/or to any Binary output contact and can also
be used with the internal user programmable logic. This allows the relay to provide panel indications and alarms.
Inverted Inputs
BI 1 inverted
Binary Input 1
INPUT
CONFIG>
BINARY
INPUT
CONFIG
BI n inverted
Binary Input n
©2010 Siemens Protection Devices Limited
BI 1 P/U Delay
=1
BI n P/U Delay
=1

Figure 2.8-1 Binary Input Logic

7SR224 Argus Description of Operation
BI 1 D/O Delay
BI 1
Event
BI n D/O Delay
BI n
Event
INPUT CONFIG>
INPUT MATRIX
(Or gates)
Logic signals,
e.g. '51-1 Inhibit'
Chapter 1 Page 13 of 70