Figure 3.3-1 Logic Diagram: Measured Directional Earth Fault Protection
3.3.2 Instantaneous Measured Earth Fault Protection (50G)
Four elements are provided e.g. giving the option of using two elements set to forward and two to reverse.
Each instantaneous element has independent settings for pick-up current 50G-n Setting and a follower time
delay 50G-n Delay. The instantaneous elements have transient free operation.
For the directional elements the direction of operation can be set using 50G-n Dir. Control setting. Directional
logic is provided independently for each 50G-n element.
Operation of the instantaneous measured earth fault elements can be inhibited from:
Inhibit 50G-n
79 E/F Inst Trips: 50G-n
50G-n Inrush Action: Inhibit
50G-n VTSAction: Inhibit
Figure 3.3-2 Logic Diagram: Measured Instantaneous Earth-fault Element
©2010 Siemens Protection Devices Limited
A binary or virtual input, or function key
When 'delayed' trips only are allowed in the autoreclose sequence
(79 E/F Prot'n Trip n = Delayed).
Operation of the current inrush detector function.
Operation of the VT Supervision function.
7SR224 Argus Description of Operation
Chapter 1 Page 24 of 70