Voltage Protection: Phase Under/Over Voltage (27/59); Figure 3.10-1 Logic Diagram: Under/Over Voltage Elements (27/59) - Siemens 7SR224 Technical Manual

Recloser controller
Hide thumbs Also See for 7SR224:
Table of Contents

Advertisement

3.10 Voltage Protection: Phase Under/Over Voltage (27/59)

In total five under/over voltage elements are provided. Four elements are provided for the 'Phase' Voltages and
one for the 'Auxiliary' input voltage.
The relay utilises fundamental frequency RMS voltage for this function. All under/over voltage elements have a
common setting to measure phase to phase (Ph-Ph) or phase to neutral (Ph-N) voltage using the Voltage Input
Mode setting.
Voltage elements can be blocked if all phase voltages fall below the 27/59 U/V Guard setting.
27/59-n (27/59-Vx) Setting sets the pick-up voltage level for the element.
The sense of the element (undervoltage or overvoltage) is set by the 27/59-n Operation (27/59-Vx Operation)
setting.
The 27/59-n O/P Phases setting determines whether the time delay is initiated for operation of any phase or only
when all phases have detected the appropriate voltage condition. An output is given after elapse of the 27/59-n
Delay (27/59-Vx Delay) setting.
The 27/59-n Hysteresis (27/59-Vx Hysteresis) setting allows the user to vary the pick-up/drop-off ratio for the
element.
Operation of the under/over voltage elements can be inhibited from:
Inhibit 27/59-n
27/59-n VTSInhibit: Yes
27/59-n U/V Guarded

Figure 3.10-1 Logic Diagram: Under/Over Voltage Elements (27/59)

©2010 Siemens Protection Devices Limited
A binary or virtual input.
Operation of the VT Supervision function.
Under voltage guard element.
7SR224 Argus Description of Operation
Chapter 1 Page 35 of 70