2.13 59N Neutral Voltage Displacement

2.13.1 Reference (59NDT)

Parameter
Vs
Setting
t
Delay setting
d

2.13.2 Operate and Reset Level (59NDT)

Attribute
V
Operate level
op
Reset level
Repeatability
-10 °C to +55 °C
Variation
f
- 3 Hz to f
nom

2.13.3 Operate and Reset Time (59NDT)

Attribute
t
Element basic operate time
basic
t
Operate time following delay
op
Repeatability
Overshoot time
Disengaging time

2.13.4 Reference (59NIT)

Parameter
M
Multiplier setting
Vs
Setting
t
Delay setting
d
t
Reset setting
res

2.13.5 Operate and Reset Level (59NIT)

Attribute
V
Operate level
op
Reset level
Repeatability
-10 °C to +55 °C
Variation
f
- 3 Hz to f
nom
©2010 Siemens Protection Devices Limited
Value
1, 1.5... 100V
0.00, 0.01...20.00, 20.50... 100, 101... 1000, 1010... 10000,
10100... 14400 s
Value
100 % Vs, ± 2 % or ± 0.5 V
≥ 95 % V
or V
op
± 1 %
≤ 5 %
≤ 5 %
+ 2 Hz
nom
Value
0V to 1.5 xVs, 76 ms, ± 20ms
0V to 10 xVs, 63 ms, ± 20ms
, ± 1 % or ± 20ms
t
+ t
basic
d
± 1 % or ± 20ms
< 40 ms
< 50 ms
Value
0.1, 0.2... 10, 10.5... 140
1, 1.5... 100V
0, 0.01... 20 s
0, 1...60 s
Value
105 % Vs, ± 2 % or ± 0.5 V
≥ 95 % V
or V
op
± 1 %
≤ 5 %
+ 2 Hz
≤ 5 %
nom
7SR224 Argus Performance Specification
± 0.25V
op
± 0.25V
op
Chapter 3 Page 36 of 49