AC Energising Quantities

Voltage and current measurement for each input channel is displayed in the Instrumentation Mode sub-menus,
each input should be checked for correct connection and measurement accuracy by single phase secondary
injection at nominal levels. Ensure that the correct instrument displays the applied signal within limits of the
Performance Specification.
Applied Current........................
I
I
A
Secondary
Primary
Apply 3P balanced Current and Voltage at nominal levels and ensure that the measured Zero Phase Sequence
and Negative Phase Sequence quantities are approximately zero.
Voltage
Current
©2010 Siemens Protection Devices Limited
I
I
B
C
G
ZPS
7SR224 Argus Commissioning & Maintenance Guide
Applied Voltage.....................
I
V
/V
V
/V
SEF
A
AB
B
BC
NPS
V
/V
V
C
CB
X