Inject 1A of balanced current. Gradually increase imbalance current, operating level should be as follows:
46BC Setting
20%
25%
30%
35%
40%
46BC Setting
3P balanced current (A)
Apply 1A 1P unbalance current without 3P balanced current. Measure 46BC operating time.
46BC Delay setting
3.5.1.1
Element Blocking
The Broken Conductor element can be blocked by Binary Input Inhibit. This functionality should be checked.
Element
©2010 Siemens Protection Devices Limited
1P unbalance current
(% of 3P current)
75%
100%
129%
161%
200%
1P unbalance current (A)
Measured
46BC
7SR224 Argus Commissioning & Maintenance Guide
Measured Unbalance current