Siemens 7SR224 Technical Manual page 278

Recloser controller
Hide thumbs Also See for 7SR224:
Table of Contents

Advertisement

F
U/O
DTL
(Hertz)
(sec)
If the element is set as 81-nU/V Guarded, this setting can be tested by applying the test voltage at a level below
the 81 U/V Guard Setting at a frequency in the operate range. Increase the voltage until the relay operates.
UVG
UVG Setting
(Volts)
U/O
Freq
2.12.8.1
Element Blocking
The U/O Frequency elements can be blocked by Binary Input Inhibit. This functionality should be checked.
Element
81-1
81-2
81-3
81-4
81-5
81-6
Check correct indication, trip output, alarm contacts, waveform record.
When testing is complete reinstate any of the disabled functions.
©2010 Siemens Protection Devices Limited
Hyst.
D.O.
P.U.
(calc.)
Freq
Hertz
Freq element
Blocked
Used for test
Volts (D.O.)
7SR224 Argus Commissioning & Maintenance Guide
D.O.
Operate
UV
Freq.
Time
Guard
Hertz
+/- 0.5Hz
Unblocked Volts (P.U.)
BI Inhibits
NOTES
NOTES
Chapter 6 Page 52 of 73