Inrush Detector (81Hbl2); Figure 5.6-1 Logic Diagram: Harmonic Block Feature (81Hbl2) - Siemens 7SR224 Technical Manual

Recloser controller
Hide thumbs Also See for 7SR224:
Table of Contents

Advertisement

5.7

Inrush Detector (81HBL2)

Inrush restraint detector elements are provided, these monitor the line currents.
The inrush restraint detector can be used to block the operation of selected elements during transformer
magnetising inrush conditions.
The 81HBL2 Bias setting allows the user to select between Phase, Sum and Cross methods of measurement:
Each phase is inhibited separately.
Phase
With this method the square root of the sum of the squares of the second harmonic in each
Sum
phase is compared to each operate current individually.
All phases are inhibited when any phase detects an inrush condition.
Cross
An output is given where the measured value of the second harmonic component is above the 81HBL2 setting.
Figure 5.7-1 Logic Diagram: Harmonic Block Feature (81HBL2)
©2010 Siemens Protection Devices Limited
7SR224 Argus Description of Operation